2021-03-19 15:34:40 | PLAN REVIEW / ROOFING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| PREVIOUS |
| |
| |
| NOTICE: SITE SPECIFIC DESIGN WIND LOADS PER FBC R301 |
| TABLE R301.2(2) (-89.4PSF) AND TABLE R301.2(3) |
| (ADJUSTMENT COEFFICIENT OF 1.21 ARE -108.17PSF |
| PRODUCT APPROVAL FL16717-R10 PROVIDES A MDP OF -60.0PSF |
| (SYSTEM W-124 SELECTED) |
| |
| 1. PROVIDE ENHANCED FASTENER CALCULATIONS FOR ZONES 2 |
| AND 3 PREPARED BY A DESIGN PROFESSIONAL. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| NEW COMMENTS: |
| |
| 1. SYSTEMS W-122, W-126 AND W-129 WOULD GIVE YOU A |
| DESIGN PRESSURE OF -112.5 AND WOULD BE APPROVED FOR |
| INSTALLATION. |
| |
| 2. PRODUCT APPROVAL 17442-R5 (LIQUID APPLIED ROOF |
| SYSTEMS), WAS SUBMITTED FOR REVIEW. SYSTEM C-17 IS |
| SELECTED TO BE INSTALLED. THIS SYSTEM IS FOR CONCRETE |
| DECKS. |
| ARE YOU PROPOSING A CHANGE IN THE SCOPE OF WORK? IF SO, |
| PROVIDE A CHANGE ORDER, SIGNED BY OWNER. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| PROVIDE CLARIFICATION. |