Plan Review Notes For Permit 21020584 |
Permit Number |
21020584 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-25 16:46:27 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) VALUE OF SYSTEM IS NOT PER INDUSTRY STANDARD. PLEASE | | SUBMIT A VALUE WHICH WILL REFLECT YOUR CONTRACT PRICE. | | | | 2) PAGE E2 50A BREAKER IS BEING MOUNTED WHERE IN THE | | 400A DISCONNECT? NOTE 3 TO BE DONE PER MANUFACTURERS | | SPECIFICATION AND LISTING. 110.3 | | | | 3) PAGE E3 REFERNCES PAGES E20 AND E30 NOT IN THIS SET | | OF PLANS. | | | | 4) PAGE E8 WHICH ONE OF THE DIAGRAMS ARE YOU USING? | | | | 5) PAGE E9 PANEL SHOWN WILL NEED A LISTING 110.3 | | | | 6) PAGE E10, E12, E13 WHICH DETAILS ARE YOU USING? | | PLEASE IDENTIFY WHICH ONE GOES WITH THIS SYSTEM. | | | | |
|