2021-03-25 16:46:27ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF SYSTEM IS NOT PER INDUSTRY STANDARD. PLEASE
 SUBMIT A VALUE WHICH WILL REFLECT YOUR CONTRACT PRICE.
  
 2) PAGE E2 50A BREAKER IS BEING MOUNTED WHERE IN THE
 400A DISCONNECT? NOTE 3 TO BE DONE PER MANUFACTURERS
 SPECIFICATION AND LISTING. 110.3
  
 3) PAGE E3 REFERNCES PAGES E20 AND E30 NOT IN THIS SET
 OF PLANS.
  
 4) PAGE E8 WHICH ONE OF THE DIAGRAMS ARE YOU USING?
  
 5) PAGE E9 PANEL SHOWN WILL NEED A LISTING 110.3
  
 6) PAGE E10, E12, E13 WHICH DETAILS ARE YOU USING?
 PLEASE IDENTIFY WHICH ONE GOES WITH THIS SYSTEM.
  
  