2021-02-23 11:22:401ST REVIEW FBC-2020 RES.
 PERMIT- 21020545
 2/23/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER IS INCOMPLETE. PLEASE PROVIDE THE
 FOLLOWING LIST OF ITEMS ON THE DRAWING IN COMPLIANCE
 WITH FBC- 2020 RES. FUEL GAS CODE:
  
 A) LABEL THE METER AS EITHER NEW OR EXISTING AND SHOW
 THE DELIVERY PRESSURE- SECTION G2413.2.
  
 B) DELIVERY PRESSURE AT REGULATOR- G2413.3 & G2421.1.
  
 C) COPPER PIPE SIZES- MAIN SUPPLY PIPE AT METER AND
 BRANCHES- G2413.4.1 & G2413.4.2.
  
 D) PROVIDE THE CORRECT BTUH OF THE TANKLESS WATER
 HEATER. THE SUBMITTED SPECS HAS A HIGHLIGHT INDICATING
 150,000 BTUH HOWEVER THE RISER INDICATES 199,000 BTUH.
  
 E) PLEASE LABEL THE APPLIANCES AS NEW OR EXISTING. THE
 RISER SHOWS A POOL HEATER NOT INCLUDED IN THE PERMIT
 APPLICATION- SECTION 107.2.1 WPB. PLEASE NOTE THAT A
 COMPLETE RISER DRAWING FOR THE SYSTEM SHALL BE
 SUBMITTED THAT INCLUDES ALL EXISTING PIPING AND
 APPLIANCES IN ORDER TO ENSURE A SAFER OPERATING SYSTEM-
 PLEASE SEE SECTIONS G2412.3 & G2412.4 FBC RES.
  
 F) PIPE SIZING TABLES USED- FBC RES. FUEL GAS- 2020 7TH
 EDITION, OR FBC- 2020 7TH EDITION FUEL GAS. PLEASE NOTE
 THE SUBMITTED PIPE SIZING TABLE IS FROM THE OUTDATED
 2017 CODE- SECTION G2413.3.
  
 G) SHOW THE LOCATIONS OF SHUT OFF VALVES AND
 REGULATORSD AT APPLIANCES- SECTIONS 2420.1 & 2421.1 FBC
 RES. GAS.
  
 2) THE RISER AND THE FLAT LINE GAS DRAWING SHALL EACH
 BEAR THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR
 OR QUALIFIER OF RECORD, AND SHALL ALSO INDICATE THE
 PROJECT ADDRESS- SECTION 107.2.1 WPB.
  
 3) SUBMIT SPECS FOR THE NEW RANGE AND POOL HEATER-
 SECTION G2431.1 FBC RES.GAS.
  
 4) SUBMIT THE CORRECT OUTLET AND INLET PRESSURE TABLE
 FOR THE B42 REGULATOR. THE TABLE IN THE SUBMITTAL IS
 FOR AN OUT PRESSURE OF 2 PSI. YOU SHOULD BE DROPPING
 PRESSURE FROM 2 PSI TO A LOW- PRESSURE SYSTEM. PLEASE
 NOTE THE NAVIEN WH SPECS INDICATE AN INLET PRESSURE OF
 10.5 IN/WC- SECTION 2421.1 FBC RES.GAS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  