Plan Review Notes
Plan Review Notes For Permit 21020498
Permit Number 21020498
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-05 13:40:331ST REVIEW FBC-2020 RES.
 PERMIT- 21020498
 4/5/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 BOTH THE NEW AND EXISTING GAS PIPING AND APPLIANCES AT
 THE RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER
 TO FBC RES. CHAPTER 24 FUEL GAS.
  
 2) PLEASE CORRECT THE 864,000 BTU GENERATOR LOAD TO
 756,000 AS LISTED IN THE SUBMITTED GENERATOR SPECS-
 SECTION 107.2.1 WPB.
  
 3) SURVEY: PLEASE CORRECT THE 5' GENERATOR DISTANCE
 FROM OPENINGS TO 10' IN COMPLIANCE WITH R305.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  