Plan Review Notes For Permit 21020498 |
Permit Number |
21020498 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-11 14:01:13 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PLEASE REVISE NOTES ON THE SURVEY. THE GENERATOR | | EXHAUST SHALL BE LOCATED 10 FEET FROM ANY OPENINGS INTO | | A BUILDING. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL | | AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE | | LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY | | HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | |
|