2021-02-24 09:45:54 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) PLEASE SHOW A ONE LINE DIAGRAM SHOWING THE |
| DISCONNECTING MEANS AT EACH BUILDING. 225.32 |
| |
| 225.32 LOCATION. THE DISCONNECTING MEANS SHALL BE |
| INSTALLED EITHER INSIDE OR OUTSIDE OF THE BUILDING OR |
| STRUCTURE SERVED OR WHERE THE CONDUCTORS PASS THROUGH |
| THE BUILDING OR STRUCTURE. THE DISCONNECTING MEANS |
| SHALL BE AT A READILY ACCESSIBLE LOCATION NEAREST THE |
| POINT OF ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES |
| OF THIS SECTION, THE REQUIREMENTS IN 230.6 SHALL BE |
| UTILIZED. |
| |
| 2) PLEASE SHOW THE GROUNDING AT EACH BUILDING FOR EACH |
| SYSTEM WHERE MULTIPLE SYSTEMS ARE LOCATED IN EACH |
| BUILDING 690.47 |
| |
| 690.47 GROUNDING ELECTRODE SYSTEM. (A) BUILDINGS OR |
| STRUCTURES SUPPORTING A PV ARRAY. A BUILDING OR |
| STRUCTURE SUPPORTING A PV ARRAY SHALL HAVE A GROUNDING |
| ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH PART III |
| OF ARTICLE?250. PV ARRAY EQUIPMENT GROUNDING CONDUCTORS |
| SHALL BE CONNECTED TO THE GROUNDING ELECTRODE SYSTEM OF |
| THE BUILDING OR STRUCTURE SUPPORTING THE PV ARRAY IN |
| ACCORDANCE WITH PART VII OF ARTICLE 250. THIS |
| CONNECTION SHALL BE IN ADDITION TO ANY OTHER EQUIPMENT |
| GROUNDING CONDUCTOR REQUIREMENTS IN 690.43(C). THE PV |
| ARRAY EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED IN |
| ACCORDANCE WITH 690.45 |
| |
| 3) I'M NOT SURE HOW TO DETERMINE THE NUMBER OF ARRAYS |
| ON EACH BUILDING 740,750,760 (750 STATES 229, -177?) |
| (740 20, 99?) (760 14, 78?) |
| |
| 4) PLEASE INDICATE HOW THE REQUIREMENTS OF LABELING PER |
| 690.56 (B) AND (C) |
| |
| 690.56 IDENTIFICATION OF POWER SOURCES. |
| (B) FACILITIES WITH UTILITY SERVICES AND PHOTOVOLTAIC |
| SYSTEMS. PLAQUES OR DIRECTORIES SHALL BE INSTALLED IN |
| ACCORDANCE WITH 705.10. |
| (C) BUILDINGS WITH RAPID SHUTDOWN. BUILDINGS WITH PV |
| SYSTEMS SHALL HAVE PERMANENT LABELS AS DESCRIBED IN |
| 690.56(C)(1) THROUGH (C)(3). (1) RAPID SHUTDOWN TYPE. |
| THE TYPE OF PV SYSTEM RAPID SHUTDOWN SHALL BE LABELED |
| AS DESCRIBED IN 690.56(C)(1)(A) OR (1)(B): |
| (3) RAPID SHUTDOWN SWITCH. A RAPID SHUTDOWN SWITCH |
| SHALL HAVE A LABEL LOCATED ON OR NO MORE THAN 1 M (3 |
| FT) FROM THE SWITCH THAT INCLUDES THE FOLLOWING |
| WORDING: RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM |
| |
| 5) PLEASE INDICATE ON THE PLANS OF EACH BUILDING |
| INVOLVED FOR THIS SYSTEM THE LOCATION OF THE |
| DISCONNECTS AND THE IDENTIFICATION OF THEM PER 225.37, |
| AND 705.10 |
| |
| 225.37 IDENTIFICATION. WHERE A BUILDING OR STRUCTURE |
| HAS ANY COMBINATION OF FEEDERS, BRANCH CIRCUITS, OR |
| SERVICES PASSING THROUGH IT OR SUPPLYING IT, A |
| PERMANENT PLAQUE OR DIRECTORY SHALL BE INSTALLED AT |
| EACH FEEDER AND BRANCH-CIRCUIT DISCONNECT LOCATION |
| DENOTING ALL OTHER SERVICES, FEEDERS, OR BRANCH |
| CIRCUITS SUPPLYING THAT BUILDING OR STRUCTURE OR |
| PASSING THROUGH THAT BUILDING OR STRUCTURE AND THE AREA |
| SERVED BY EACH. |
| |
| 705.10 DIRECTORY. A PERMANENT PLAQUE OR DIRECTORY |
| DENOTING THE LOCATION OF ALL ELECTRIC POWER SOURCE |
| DISCONNECTING MEANS ON OR IN THE PREMISES SHALL BE |
| INSTALLED AT EACH SERVICE EQUIPMENT LOCATION AND AT THE |
| LOCATION(S) OF THE SYSTEM DISCONNECT(S) FOR ALL |
| ELECTRIC POWER PRODUCTION SOURCES CAPABLE OF BEING |
| INTERCONNECTED. THE MARKING SHALL COMPLY WITH |
| 110.21(B). |
| |
| |