2021-02-24 09:45:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE SHOW A ONE LINE DIAGRAM SHOWING THE
 DISCONNECTING MEANS AT EACH BUILDING. 225.32
  
 225.32 LOCATION. THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF THE BUILDING OR
 STRUCTURE SERVED OR WHERE THE CONDUCTORS PASS THROUGH
 THE BUILDING OR STRUCTURE. THE DISCONNECTING MEANS
 SHALL BE AT A READILY ACCESSIBLE LOCATION NEAREST THE
 POINT OF ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES
 OF THIS SECTION, THE REQUIREMENTS IN 230.6 SHALL BE
 UTILIZED.
  
 2) PLEASE SHOW THE GROUNDING AT EACH BUILDING FOR EACH
 SYSTEM WHERE MULTIPLE SYSTEMS ARE LOCATED IN EACH
 BUILDING 690.47
  
 690.47 GROUNDING ELECTRODE SYSTEM. (A) BUILDINGS OR
 STRUCTURES SUPPORTING A PV ARRAY. A BUILDING OR
 STRUCTURE SUPPORTING A PV ARRAY SHALL HAVE A GROUNDING
 ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH PART III
 OF ARTICLE?250. PV ARRAY EQUIPMENT GROUNDING CONDUCTORS
 SHALL BE CONNECTED TO THE GROUNDING ELECTRODE SYSTEM OF
 THE BUILDING OR STRUCTURE SUPPORTING THE PV ARRAY IN
 ACCORDANCE WITH PART VII OF ARTICLE 250. THIS
 CONNECTION SHALL BE IN ADDITION TO ANY OTHER EQUIPMENT
 GROUNDING CONDUCTOR REQUIREMENTS IN 690.43(C). THE PV
 ARRAY EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED IN
 ACCORDANCE WITH 690.45
  
 3) I'M NOT SURE HOW TO DETERMINE THE NUMBER OF ARRAYS
 ON EACH BUILDING 740,750,760 (750 STATES 229, -177?)
 (740 20, 99?) (760 14, 78?)
  
 4) PLEASE INDICATE HOW THE REQUIREMENTS OF LABELING PER
 690.56 (B) AND (C)
  
 690.56 IDENTIFICATION OF POWER SOURCES.
 (B) FACILITIES WITH UTILITY SERVICES AND PHOTOVOLTAIC
 SYSTEMS. PLAQUES OR DIRECTORIES SHALL BE INSTALLED IN
 ACCORDANCE WITH 705.10.
 (C) BUILDINGS WITH RAPID SHUTDOWN. BUILDINGS WITH PV
 SYSTEMS SHALL HAVE PERMANENT LABELS AS DESCRIBED IN
 690.56(C)(1) THROUGH (C)(3). (1) RAPID SHUTDOWN TYPE.
 THE TYPE OF PV SYSTEM RAPID SHUTDOWN SHALL BE LABELED
 AS DESCRIBED IN 690.56(C)(1)(A) OR (1)(B):
 (3) RAPID SHUTDOWN SWITCH. A RAPID SHUTDOWN SWITCH
 SHALL HAVE A LABEL LOCATED ON OR NO MORE THAN 1 M (3
 FT) FROM THE SWITCH THAT INCLUDES THE FOLLOWING
 WORDING: RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM
  
 5) PLEASE INDICATE ON THE PLANS OF EACH BUILDING
 INVOLVED FOR THIS SYSTEM THE LOCATION OF THE
 DISCONNECTS AND THE IDENTIFICATION OF THEM PER 225.37,
 AND 705.10
  
 225.37 IDENTIFICATION. WHERE A BUILDING OR STRUCTURE
 HAS ANY COMBINATION OF FEEDERS, BRANCH CIRCUITS, OR
 SERVICES PASSING THROUGH IT OR SUPPLYING IT, A
 PERMANENT PLAQUE OR DIRECTORY SHALL BE INSTALLED AT
 EACH FEEDER AND BRANCH-CIRCUIT DISCONNECT LOCATION
 DENOTING ALL OTHER SERVICES, FEEDERS, OR BRANCH
 CIRCUITS SUPPLYING THAT BUILDING OR STRUCTURE OR
 PASSING THROUGH THAT BUILDING OR STRUCTURE AND THE AREA
 SERVED BY EACH.
  
 705.10 DIRECTORY. A PERMANENT PLAQUE OR DIRECTORY
 DENOTING THE LOCATION OF ALL ELECTRIC POWER SOURCE
 DISCONNECTING MEANS ON OR IN THE PREMISES SHALL BE
 INSTALLED AT EACH SERVICE EQUIPMENT LOCATION AND AT THE
 LOCATION(S) OF THE SYSTEM DISCONNECT(S) FOR ALL
 ELECTRIC POWER PRODUCTION SOURCES CAPABLE OF BEING
 INTERCONNECTED. THE MARKING SHALL COMPLY WITH
 110.21(B).
  
  