2021-02-24 16:31:15 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21020437 |
| 2/24/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A2.0: PROVIDE A WATER RISER AND A FLAT LINE DRAWING |
| SHOWING HOW WATER WILL BE SUPPLIED TO THE ISLAND SINK, |
| DISHWASHER, AND REFRIGERATOR ICE MAKER - SECTION |
| 103.5.1.3 WPB. SHGOW LOCATIONS OF WARTER HAMMER |
| ARRESTORS AND BACKFLOW PREVENTERS- SECTION 604.9 & |
| 608.3 FBC P. |
| |
| 2) A2.0: SHOW THE SHUTOFF VALVES FOR THE WASHING |
| MACHINE WILL BE RELOCATED TO A LOCATION WITH ACCESS- |
| SECTION 606.3 FBC P. |
| |
| 3) A2.0: REFER TO SECTION 1002.1 FBC P- THE HORIZONTAL |
| DISTANCE FROM THE CENTERLINE OF THE NEW TUB DRAIN |
| OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING |
| TRAP SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE |
| PLAN INDICATING COMPLIANCE. |
| |
| 4) A2.0: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| SECTION 315.1 FBC P, AND SECTION 714.4.1.2 FBC B. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |