2021-02-17 12:51:06 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21020437 |
| ADD: 1900 CONSULATE PL. SUITE: 2202 |
| CONT: BUILD & FIX INC. |
| TEL: 561-908-3212 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 17TH/ 2021 |
| ACTION: DENIED |
| |
| 1) EXISTING & PROPOSED FLOOR PLAN: |
| 1A) GYPSUM BOARD PARTITIONS & CEILINGS. THIS WHOLE |
| HEADING REFERS MOSTLY TO R-3 CONSTRUCTION. WITH 2 X4 |
| STUD WALLS, CEILINGS FASTENED TO BOTTOM CHORD OF WOOD |
| TRUSSES. PLEASE REFER TO THE 2020 FBC-B SECTION 603.1.1 |
| WHERE FIRE RETARDANT TREATED WOOD CAN BE INSTALLED. |
| |
| 1B) DESIGN PARAMETERS REFERS TO ASCE-7-10. THIS WAS THE |
| VERSION OF THE ASCE-7 UNDER THE 2017 FBC-B. UNDER THE |
| 2020 FBC-B THE ASCE 7 VERSION IS ASCE 7-16. PLEASE |
| UPDATE CHAPTER 35 OF THE 2020 FBC-B. |
| |
| 1C) THERE ARE DESIGN PARAMETER NOTES THAT DO NOT |
| PERTAIN TO THIS PROJECT, TOP CHORD, BOTTOM CHORD LOADS, |
| SOIL BEARING CAPACITY, PLEASE REMOVE. 2020 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION 107.2.1. W.P.B. ADMINISTRATIVE |
| CODE/2017 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| |
| 1D) DESIGN PARAMETERS, THE MEAN ROOF HEIGHT IS GIVEN AT |
| 30 FEET, THEN AGAIN, THE PLANS STATE THE NUMBER OF |
| STORIES AS 12 STORIES. PLEASE NOTE THIS IS A 22 STORY |
| HIGHRISE BUILDING. UPDATE PLANS. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 1E) THE DESIGN PARAMETERS LIST THE CONSTRUCTION TYPE AS |
| IIB. PLEASE REFER TO TABLE 504.4 ALLOWABLE NUMBER OF |
| STORIES ABOVE GRADE. FOR A 22-STORY BUILDING R-2 |
| OCCUPANCY THE MINIMUM BUILDING TYPE IS I-A. |
| |
| 1F) CODE REQUIREMENTS ALSO LIST TYPE OF CONSTRUCTION |
| CHAPTER 6 TYPE II-B SPRINKLERED. . PLEASE REFER TO |
| TABLE 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE. |
| FOR A 22-STORY BUILDING R-2 OCCUPANCY THE MINIMUM |
| BUILDING TYPE IS I-A. |
| |
| SCOPE OF WORK: |
| |
| 1G) NOTE 5, 6 & 15 ALL DEAL WITH THE EITHER RAISING OR |
| DROPPING THE CEILINGS IN THE ENTRANCE, BATHROOMS AND |
| KITCHEN AREAS. |
| AS THE DESIGNER OF RECORD PLEASE PROVIDE THE TYPE OF |
| MATERIALS FOR THE FRAMING MEMBERS OF THE DROPPED |
| CEILINGS, SPAN, SIZE OF THE METAL STUDS, WILL THERE BE |
| MIDSPAN SUPPORTS AND THICKNESS OF DRYWALL FINISH. |
| |
| 1H)(1) NOTE 18 INDICATES THE INSTALLATION OF A NEW |
| GLASS DOOR. PLEASE PROVIDE THE LOCATION. IF THIS DOOR |
| IS AN EXTERIOR DOOR PLEASE ALSO PROVIDE THE PRODUCT |
| APPROVAL FOR THE DOOR. 2020 FBC-B 1609.1.2 PROTECTION |
| OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS |
| |
| 1H)(2) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 2) NOTE 19 INDICATES THE REMOVAL AND REPLACEMENT OF ALL |
| FLOORS. TYPE OF FLOOR FINISH NOT GIVEN. FLOOR |
| INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE, VINYL |
| AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| THE 2017 FBC-B. |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |