2021-05-27 10:33:08 | THE CURRENT PLANS ARE APPROVED WITH EXCEPTION. |
| A REVISION TO THE APPROVED PLANS IS REQUIRED TO EITHER |
| RELOCATE THE GAS GRILL AND PIZZA OVEN FROM BELOW THE |
| COMBUSTIBLE TRELLIS, OR MODIFY THE TRELLIS TO MAKE IT A |
| NON-COMBUSTIBLE STRUCTURE. |
| CCOLE- 5/27/2021 |
| |
| 2ND REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21020420 |
| 5/13/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE |
| AFPO-C ARTISAN FIRE PIZZA OVEN AND THE K750HB HYBRID |
| FIRE GRILL EACH HAVE THIS STATEMENT PRINTED ON THEIR |
| FRONT PAGES- "NEVER PLACE (OVEN) (GRILL) UNDERNEATH AN |
| OVERHEAD COMBUSTIBLE STRUCTURE". THE ARCHITECTURAL PLAN |
| APPEARS TO INDICATE AN EXISTING WOOD FRAME ROOF OR |
| TRELLIS ABOVE IT. THE INSTALLATIONS ARE DENIED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |