2021-05-13 09:20:25 | 2ND REVIEW FBC-2020 RES. FUE GAS |
| PERMIT- 21020420 |
| 5/13/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1)) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE |
| AFPO-C ARTISAN FIRE PIZZA OVEN AND THE K750HB HYBRID |
| FIRE GRILL EACH HAVE THIS STATEMENT PRINTED ON THEIR |
| FRONT PAGES- "NEVER PLACE (OVEN) (GRILL) UNDERNEATH AN |
| OVERHEAD COMBUSTIBLE STRUCTURE". THE ARCHITECTURAL PLAN |
| APPEARS TO INDICATE AN EXISTING WOOD FRAME ROOF OR |
| TRELLIS ABOVE IT. THE INSTALLATIONS ARE DENIED. |
| |
| 2) THE SUBMITTAL FOR THE GOVERNOR GAS REGULATORS |
| INDICATES OUTLET PRESSURES OF 8- 11 IN. W.C., HOWEVER |
| THE NEW OVEN AND GRILL HAVE INPUT PRESSURES OF 7 IN. |
| W.C. PLEASE SPECIFY THE CORRECT REGULATORS FOR THE |
| INSTALLATIONS- SECTION G2421.2 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |