Date |
Text |
2021-03-17 08:36:04 | 1ST REVIEW FBC-2020 RES. FUE GAS |
| PERMIT- 21020420 |
| 3/17/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES |
| ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE |
| RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO |
| FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| F) TYPES AND SIZES OF PIPING. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. PLEASE LIST THE MAKE |
| AND SELECTED MODEL REGULATOR ON THE DRAWING. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BBQ |
| GRILL AND PIZZA OVEN- SECTION G2406.1, G2406.3, G2447.1 |
| FBC RES. PLEASE REVIEW THE INSTALLATION GUIDELINES AND |
| SHOW ALL REQUIRED CLEARANCES TO COMBUSTIBLES, OVERHEAD |
| ROOF CONSTRUCTION AND OPENINGS INTO THE BUILDING. IT |
| APPEARS THE NEW APPLIANCES ARE BEING INSTALLED IN A |
| PARTIALLY ENCLOSED COMBUSTIBLE STRUCTURE WHICH MAY BE |
| PROHIBITED PER MANUFACTURER'S SPECIFICATIONS, AND MAY |
| ALSO REQUIRE INSTALLATION OF EXHAUST HOODS. PLEASE NOTE |
| THAT A MINIMUM 10 FT. CLEARANCE FROM THE EXHAUST OF THE |
| APPLIANCES TO AIR INTAKES AND OPENINGS INTO THE |
| BUILDINGS SUCH AS OPERABLE DOORS AND WINDOWS IS |
| REQUIRED UNDER SECTION R303.5.1 FBC RES. MANUFACTURER?S |
| SPECIFICATIONS AND INSTALLATIONS ARE REQUIRED TO BE |
| ONSITE AT TIME OF INSPECTION- SECTION G2408.1 & G2447.1 |
| FBC RES. |
| |
| 3) SUBMIT MANUFACTURER'S SPECIFICTIONS FOR NEW GAS |
| REGULATORS MARKED OR HIGHLISHTED TO SHOW THE SELECTED |
| MODELS, INLET AND OUTLET PRESSURES, AND ORIFICE SIZES- |
| SECTION G2421 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |