2021-03-17 08:36:041ST REVIEW FBC-2020 RES. FUE GAS
 PERMIT- 21020420
 3/17/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) TYPES AND SIZES OF PIPING.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS. PLEASE LIST THE MAKE
 AND SELECTED MODEL REGULATOR ON THE DRAWING.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BBQ
 GRILL AND PIZZA OVEN- SECTION G2406.1, G2406.3, G2447.1
 FBC RES. PLEASE REVIEW THE INSTALLATION GUIDELINES AND
 SHOW ALL REQUIRED CLEARANCES TO COMBUSTIBLES, OVERHEAD
 ROOF CONSTRUCTION AND OPENINGS INTO THE BUILDING. IT
 APPEARS THE NEW APPLIANCES ARE BEING INSTALLED IN A
 PARTIALLY ENCLOSED COMBUSTIBLE STRUCTURE WHICH MAY BE
 PROHIBITED PER MANUFACTURER'S SPECIFICATIONS, AND MAY
 ALSO REQUIRE INSTALLATION OF EXHAUST HOODS. PLEASE NOTE
 THAT A MINIMUM 10 FT. CLEARANCE FROM THE EXHAUST OF THE
 APPLIANCES TO AIR INTAKES AND OPENINGS INTO THE
 BUILDINGS SUCH AS OPERABLE DOORS AND WINDOWS IS
 REQUIRED UNDER SECTION R303.5.1 FBC RES. MANUFACTURER?S
 SPECIFICATIONS AND INSTALLATIONS ARE REQUIRED TO BE
 ONSITE AT TIME OF INSPECTION- SECTION G2408.1 & G2447.1
 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICTIONS FOR NEW GAS
 REGULATORS MARKED OR HIGHLISHTED TO SHOW THE SELECTED
 MODELS, INLET AND OUTLET PRESSURES, AND ORIFICE SIZES-
 SECTION G2421 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  