2021-03-15 14:08:20 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21020406 |
| 3/15/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A UG LP TANK HOLD-DOWN DETAIL SHOWING HOW |
| THE TANK WILL BE ANCHORED TO PREVENT FLOTATION, |
| COLLAPSE, OR LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA-58. |
| PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT |
| SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, AND |
| THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| CABLES OR STRAPS. |
| |
| 2) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION |
| BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM |
| CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED |
| CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA |
| 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1. |
| |
| 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FIRE |
| BOWLS- SECTION G2454.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |