Plan Review Notes
Plan Review Notes For Permit 21020406
Permit Number 21020406
Review Stop G
Sequence Number 1
Notes
Date Text
2021-03-15 14:08:201ST REVIEW FBC-2020 RES.
 PERMIT- 21020406
 3/15/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A UG LP TANK HOLD-DOWN DETAIL SHOWING HOW
 THE TANK WILL BE ANCHORED TO PREVENT FLOTATION,
 COLLAPSE, OR LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA-58.
 PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT
 SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, AND
 THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
  
 2) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION
 BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM
 CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED
 CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA
 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FIRE
 BOWLS- SECTION G2454.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.