2021-04-01 14:38:58 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT |
| MATCH THE IMPACT RATED ONES SPECIFIED BY THE DESIGNER |
| OF RECORD IN THE WINDOW AND DOOR SCHEDULES ON THE |
| PLANS. THE ROOFING PRODUCT APPROVALS ARE ALSO |
| DIFFERENT. SUBMIT THE ONES THAT ARE APPROVED BY THE |
| DESIGNER OF RECORD AND LISTED ON THE PLANS. CIRCLE OR |
| HI-LIGHT THE SPECIFIC ITEMS AND DESIGN PRESSURES IN THE |
| PRODUCT APPROVALS. FBC AMENDMENTS 107.3.4 - PROVIDE TWO |
| SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| TYPES. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| ELECTRONICALLY SUBMITTED DOCUMENTS. |
| |
| 2) THE SURFACE WATER DRAINAGE PLAN DOES NOT ADEQUATELY |
| SHOW THAT THE SURFACE WATER WILL BE CONTAINED ON THE |
| LOT AND HAS A 6 INCH FALL AWAY FROM THE BUILDING. |
| PROVIDE A MORE DETAILED DRAINAGE PLAN. |
| FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED |
| TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF |
| COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE |
| GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152 |
| MM) WITHIN THE FIRST 10 FEET (3048 MM). EXCEPTION: |
| WHERE LOT LINES, WALLS, SLOPES OR OTHER PHYSICAL |
| BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL WITHIN 10 |
| FEET (3048 MM), DRAINS OR SWALES SHALL BE CONSTRUCTED |
| TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. IMPERVIOUS |
| SURFACES WITHIN 10 FEET (3048 MM) OF THE BUILDING |
| FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 PERCENT AWAY |
| FROM THE BUILDING. |
| |
| |
| |
| |
| |
| |