2021-03-09 13:29:27PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON PAGE 004, 3-4 THE FOUNDATION PLAN IS MISSING SOME
 OF THE FILLED CELLS AT THE EAST WALL OF THE DINING
 ROOM. FBC 107.2.1
  
 2) THE PRODUCT APPROVALS FOR THE WINDOWS AND DOORS HAVE
 MULTIPLE TYPES OF WINDOWS AND DOORS LISTED IN THE
 PRODUCT APPROVALS WITH DIFFERENT DESIGN PRESSURES, ETC.
 CIRCLE OR HI-LIGHT THE ITEMS THAT ARE SPECIFIC TO THIS
 PROJECT. FBC 107.2.1
  
 3) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVALS IN WRITING. FBC 107.3.4 -
 PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 4) THE PRODUCT APPROVALS FOR THE WINDOWS AND SLIDING
 GLASS DOOR ARE NOT IMPACT RATED. SUBMIT A KEY PLAN, AN
 INSTALLATION SCHEDULE AND PRODUCT APPROVALS FOR THE
 REQUIRED IMPACT PROTECTION DEVICES. FBC 107.2.1
  
 5) PROVIDE A SURFACE WATER DRAINAGE PLAN FOR THE SITE
 THAT SHOWS COMPLIANCE WITH FBC-R401.3 DRAINAGE. SURFACE
 DRAINAGE SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE
 OR OTHER APPROVED POINT OF COLLECTION THAT DOES NOT
 CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE
 WATER AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL
 A MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET
 (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
  
  
  