2021-03-10 08:00:27****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 303.4/FBC B 1010.1.10; AS THIS IS AN A-3
 (GROUP A ASSEMBLY). THEREFORE PANIC HARDWARE IS
 REQUIRED ON THE DOORS.
  
 2) FBC B 1609: PLEASE PROVIDE THE PRODUCT APPROVALS FOR
 THE PROPOSED REPLACEMENT DOORS. THE PRODUCT APPROVALS
 NEED TO SHOW IMPACT RESISTANCE, WINDLOAD PRESSURE
 CAPACITY, PANIC HARDWARE & THE CONNECTION OPTIONS.
  
  
  