Plan Review Notes
Plan Review Notes For Permit 21020328
Permit Number 21020328
Review Stop B
Sequence Number 1
Notes
Date Text
2021-02-23 16:32:09WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020328
 ADD: 327 HIBISCUS ST.
 CONT: SHUTTER UP INDUSTRIES INC/ QUALIFIER JEREMY S
 KOBOSKO
 TEL: 561-588-2623
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) THE CONTRACTOR (QUALIFIER/ JEREMY S KOBOSKO) THAT
 CREATED / DREW THE SET OF PLANS SHEET 1 & 2TWILL NEED
 TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2A) THE PERMIT APPLICATION INDICATES THE REPLACEMENT OF
 4 PICTURE WINDOWS AND 1 EXTERIOR DOOR. THE FLOOR PLAN
 ONLY SHOWS 2 OPENINGS. THE WRITTEN WORDS ARE SO SMALL
 WHEN THE PLANS GO TO RECORD RETENTION, THEY MAY NOT BE
 LEGIBLE FOR RECORD RETENTION. 107.2.1.3. QUALITY OF
 PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS AND
 SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 2B) THE WORDING ON THIS DOCUMENT APPEARS THE 4 SUPPOSED
 PICTURE WINDOWS ARE MULTIPLE (2) WINDOWS IN EACH
 OPENING WITH MULLIONS, ACTUALLY 2 OPENINGS, IS THAT
 CORRECT? WHERE IS THE DOOR THAT IS GOING TO BE
 REPLACED. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 NO LOCATION IS GIVEN FOR THE DOOR MAYBE IN ZONE 4 OR 5.
  
 3) THE DESIGN PRESSURE REPORT. THE DESIGN PRESSURE
 REPORT IS NOT DESIGNED BY A PROFESSIONAL ENGINEER.
 THERE IS NO DESIGNATION AS TO WHERE THE SUBMITTED
 PRESSURES CAME FROM. CONTRACTORS CAN NOT ACT AS
 ENGINEERS, YOU MUST PULL THE DESIGN PRESSURES FROM ASCE
 7-16, THE 2020 FBC-B OR SOME OTHER RECOGNIZED SOURCE.
 ONE AND TWO FAMILY DWELLINGS THE CONTRACTOR CAN USE THE
 TABLE IN THAT CODE BOOK WITH MULTIPLIERS FOR EXPOSURE
 AND HEIGHT FOR RESIDENTIAL UNITS.
  
 4) THE DESIGN PRESSURE REPORT SUBMITTED LIST THE MEAN
 ROOF HEIGHT AS 15 FEET. GOOGLE MAPS INDICATES THIS
 BUILDING IS A 2 STORY BUILDING. THE MEAN ROOF HEIGHT IS
 HIGHER THAN 15 FEET.
  
 5) THE SUBMITTED DESIGN PRESSURE SHEET LIST THE HEIGHT
 OF THE ONE OPENING AS 92 INCHES WHEREAS THE 2ND OPENING
 THE HEIGHT IS LISTED AS 149 INCHES IN HEIGHT. MAYBE A
 TYPO. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  