2021-02-23 16:32:09 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21020328 |
| ADD: 327 HIBISCUS ST. |
| CONT: SHUTTER UP INDUSTRIES INC/ QUALIFIER JEREMY S |
| KOBOSKO |
| TEL: 561-588-2623 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: |
| ACTION: DENIED |
| |
| 1) THE CONTRACTOR (QUALIFIER/ JEREMY S KOBOSKO) THAT |
| CREATED / DREW THE SET OF PLANS SHEET 1 & 2TWILL NEED |
| TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. |
| PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE |
| NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS |
| DRAWN. |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| AND PLANS DRAWN. |
| |
| 2A) THE PERMIT APPLICATION INDICATES THE REPLACEMENT OF |
| 4 PICTURE WINDOWS AND 1 EXTERIOR DOOR. THE FLOOR PLAN |
| ONLY SHOWS 2 OPENINGS. THE WRITTEN WORDS ARE SO SMALL |
| WHEN THE PLANS GO TO RECORD RETENTION, THEY MAY NOT BE |
| LEGIBLE FOR RECORD RETENTION. 107.2.1.3. QUALITY OF |
| PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS AND |
| SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC |
| MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| OF FLORIDA STATUTES. |
| |
| 2B) THE WORDING ON THIS DOCUMENT APPEARS THE 4 SUPPOSED |
| PICTURE WINDOWS ARE MULTIPLE (2) WINDOWS IN EACH |
| OPENING WITH MULLIONS, ACTUALLY 2 OPENINGS, IS THAT |
| CORRECT? WHERE IS THE DOOR THAT IS GOING TO BE |
| REPLACED. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| NO LOCATION IS GIVEN FOR THE DOOR MAYBE IN ZONE 4 OR 5. |
| |
| 3) THE DESIGN PRESSURE REPORT. THE DESIGN PRESSURE |
| REPORT IS NOT DESIGNED BY A PROFESSIONAL ENGINEER. |
| THERE IS NO DESIGNATION AS TO WHERE THE SUBMITTED |
| PRESSURES CAME FROM. CONTRACTORS CAN NOT ACT AS |
| ENGINEERS, YOU MUST PULL THE DESIGN PRESSURES FROM ASCE |
| 7-16, THE 2020 FBC-B OR SOME OTHER RECOGNIZED SOURCE. |
| ONE AND TWO FAMILY DWELLINGS THE CONTRACTOR CAN USE THE |
| TABLE IN THAT CODE BOOK WITH MULTIPLIERS FOR EXPOSURE |
| AND HEIGHT FOR RESIDENTIAL UNITS. |
| |
| 4) THE DESIGN PRESSURE REPORT SUBMITTED LIST THE MEAN |
| ROOF HEIGHT AS 15 FEET. GOOGLE MAPS INDICATES THIS |
| BUILDING IS A 2 STORY BUILDING. THE MEAN ROOF HEIGHT IS |
| HIGHER THAN 15 FEET. |
| |
| 5) THE SUBMITTED DESIGN PRESSURE SHEET LIST THE HEIGHT |
| OF THE ONE OPENING AS 92 INCHES WHEREAS THE 2ND OPENING |
| THE HEIGHT IS LISTED AS 149 INCHES IN HEIGHT. MAYBE A |
| TYPO. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |