2021-02-17 11:54:44 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| 7TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1) FLAGLER STATION TEMP RISER SHEET DETAIL 1: IT |
| APPEARS THAT TWO DIFFERENT SIZE CONDUCTORS ARE |
| SPECIFIED FOR SERVICE ENTRANCE CONDUCTORS. ONE IS 2 |
| SETS OF 3#250 AL XHHN AND THE OTHER ONE IS 2 SETS OF |
| 3#500 + 1#500N AL. THE 2 SETS OF 3#250 AL ARE TOO SMALL |
| FOR A 600 AMPS SERVICE. PLEASE REMOVE INCONSISTENCIES |
| AND LEAVE ONLY THE CORRECT CONDUCTORS. |
| 2) PLEASE SUBMIT AVAILABLE SHORT CIRCUIT CURRENT AT |
| SERVICE PANEL. |
| 3) ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A |
| DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL |
| CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| |
| ENRIQUE QUINONEZ P.E. |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |