2021-03-19 14:06:18 | 1ST REVIEW FBC-2020 RES. |
| PERMI- 21020263 |
| 3/19/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| NFPA 58 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB. |
| REFER TO NFPA 58 AND PROVIDE: |
| |
| A) TYPES AND SIZES OF PIPING TO BE INSTALLED. |
| |
| B) DELIVERY PRESSURE AT THE TANK. |
| |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| |
| D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| |
| E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| |
| H) OUTLET PRESSURES AT REGULATORS. |
| |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES (IF APPLICABLE). |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE 250 |
| GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE BEEN |
| DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) IN |
| ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| SECTION 5.2.1.1 NFPA 58. |
| |
| 3) PROVIDE A UG LP TANK HOLD-DOWN DETAIL SHOWING HOW |
| THE TANK WILL BE ANCHORED TO PREVENT FLOTATION, |
| COLLAPSE, OR LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA-58. |
| PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT |
| SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, AND |
| THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| CABLES OR STRAPS. |
| |
| 4) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION |
| BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM |
| CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED |
| CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA |
| 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1 NFPA 58. |
| |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| REGULATORS MARKED UP TO SHOW THE SELECTED MODE, INLET |
| AND OUTLET PRESSURES AND PIPE SIZES- SECTION 6.10.1 |
| NFPA 58. |
| |
| 6) SUBMIT MANUFACTURER'S DATA SHEET FOR THE GENERATOR |
| SHOWING THE BTU LOAD AND INPUT PRESSURE- SECTION- |
| 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |