Plan Review Notes
Plan Review Notes For Permit 21020263
Permit Number 21020263
Review Stop G
Sequence Number 1
Notes
Date Text
2021-03-19 14:06:181ST REVIEW FBC-2020 RES.
 PERMI- 21020263
 3/19/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 NFPA 58
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB.
 REFER TO NFPA 58 AND PROVIDE:
  
 A) TYPES AND SIZES OF PIPING TO BE INSTALLED.
  
 B) DELIVERY PRESSURE AT THE TANK.
  
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
  
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
  
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
  
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
  
 H) OUTLET PRESSURES AT REGULATORS.
  
 I) LOCATIONS AND TYPES OF PIPE SLEEVES (IF APPLICABLE).
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE 250
 GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE BEEN
 DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) IN
 ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 3) PROVIDE A UG LP TANK HOLD-DOWN DETAIL SHOWING HOW
 THE TANK WILL BE ANCHORED TO PREVENT FLOTATION,
 COLLAPSE, OR LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA-58.
 PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT
 SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, AND
 THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
  
 4) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION
 BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM
 CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED
 CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA
 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1 NFPA 58.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP TO SHOW THE SELECTED MODE, INLET
 AND OUTLET PRESSURES AND PIPE SIZES- SECTION 6.10.1
 NFPA 58.
  
 6) SUBMIT MANUFACTURER'S DATA SHEET FOR THE GENERATOR
 SHOWING THE BTU LOAD AND INPUT PRESSURE- SECTION-
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  