Plan Review Notes For Permit 21020258 |
Permit Number |
21020258 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-29 13:53:30 | 1ST REVIEW FBC-2020 RES. | | PERMIT- 21020258 | | 12/29/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE A SANITARY DRAINAGE AND VENT ISOMETRIC | | DRAWING FOR THE NEW BATHROOM- SEC. 107.3.5.3 WPB. | | PLEASE INCLUDE THE POINT OF CONNECTION TO THE EXISTING | | SANITARY DRAIN OR SEWER LINE. | | | | 2) THE FIXTURE LAYOUT IN THE BATHROOM INDICATES THERE | | WILL NOT BE ADEQUATE SPACE TO INSTALL THE TOILET AND | | LAVATORY (CALLED FACE BASIN IN THE DRAWING). A BATHTUB | | IS TYPICALLY 5'0" IN LENGTH AND THE ROOM IS ONLY 6'8" | | IN LENGTH- SEE SEC. R307.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|