2022-03-14 13:23:53BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: INSUFICIENT INFORMATION PROVIDED FOR A
 COMPREHENSIVE REVIEW. PLEASE REFERENCE THE BELOW
 CHECKLIST.
  
 RESIDENTIAL SITE BUILT STRUCTURES. (NEW AND ADDITIONS)
  
 CHECKLIST
  
 EVERY STRUCTURE SUBJECT TO WIND LOADS SHALL BE DESIGNED
 PER FBC RES CHPT 3 OR THE FBC BLDG. CHPT. 16 AND ASCE
 7-16.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 EXCEPTION; SHEDS AND ACCESSORY STRUCTURES
 R301.2.1.2 PROTECTION OF OPENINGS.
 STRUCTURES THAT ARE NOT DESIGNED FOR HUMAN HABITATION
 AND THAT HAVE A FLOOR AREA OF 720 SQUARE FEET (67 M2)
 OR LESS ARE NOT REQUIRED TO COMPLY WITH THE MANDATORY
 WIND-BORNE DEBRIS IMPACT STANDARD OF THIS CODE.
  
 1. PROVIDE A SITE PLAN....
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE
 AND INCLUDED BOUNDARY LINE SURVEY.
  
 2. PROVIDE THE FOLLOWING BUILDING PLANS
  
 2A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING/TIE DOWNS.
 2B) PROVIDE REQUIRED DIMENSIONS.
 2C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION
 CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 2D) PROVIDE A WALL PLAN (SECTION VIEW) WITH WALL TO
 FLOOR CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 2E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL
 CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 2F) PROVIDE A WINDOW AND/OR DOOR SCHEDULE WITH ROUGH
 OPENINGS AND DESIGN WIND LOADS. (COORDINATE SCHEDULE
 WITH OPENINGS ON FLOOR PLAN).
 2G) PROVIDE PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS,
 DOORS, AND TIE DOWNS. >720 SQ. FT. SEE R301.2.1.2
 2H) ELECTRICAL PROVIDE AN ELECTRICAL PLAN. ELECTRIC
 SUB-PERMIT REQUIRED.
 2I) MECHANICAL PROVIDE A MECHANICAL PLAN. MECHANICAL
 SUB-PERMIT REQUIRED.
 2J) PLUMBING PROVIDE A PLUMBING PLAN. PLUMBING
 SUB-PERMIT REQUIRED.
 2K) ROOFING PROVIDE A ROOF PLAN. ROOFING SUB-PERMIT
 REQUIRED.
  
 3. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 4. PROVIDE A SOILS REPORT; FOR PROPERTIES LOCATED IN
 AREAS OF QUESTIONABLE SOILS, PER CITY SOILS MAP.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 5. PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  
 6. PROVIDE AN ENERGY SUBMITTAL; RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. 1.SECTIONS R401 THROUGH R404.
 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED; MANDATORY.
  
 7. SIGNATURE REQUIREMENT; DESINER, (O/B, CONTRACTOR OR
 DESIGN PROFESSIONAL) SHALL PRINT THEIR NAME AND SIGN
 EACH PLAN SHEET.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  