2021-02-23 17:20:33 | 2ND REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21020232 |
| 2/23/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| NEW COMMENTS. |
| |
| 1) GAS RISER: THE TOTAL GAS LOAD OF 1,789 MBH LISTED |
| APPEARS TO BE INCORRECT BASED ON THE INDIVIDUAL |
| APPLIANCE LOADS SHOWN WHICH ADD UP TO 994 MBH. PLEASE |
| NOTE THAT USING THE PIPE SIZING TABLE LISTED AN 1-1/4 |
| IN. GALVANIZED PIPE CAN DELIVER A MAXIMUM 1280 MBH AT |
| 63 FT. DEVELOPED LENGTH. IT ALSO APPEARS THAT ONE OF |
| THE COOKING APPLIANCES ON THE LINE IS NOT LISTED. THE |
| RISER SHOWS 7 PIPE OUTLETS ON THE LINE BUT ONLY 6 |
| COOKING APPLIANCES ARE LISTED. |
| |
| 2) GAS RISER: INDICATE THE TYPE AND SIZE OF PIPE |
| SUPPLYING THE WATER HEATER, AND THE SIZE AND LENGTH OF |
| THE MAIN SUPPLY PIPE FROM THE METER TO THE FIRST TEE- |
| SECTION 402.2 & 402.3 FBC FG. |
| |
| 3) THE CONTRACTOR OR QUALIFIER SHALL PROVIDE HIS |
| SIGNATURE ON THE DRAWING- SECTION 107.2.1 WPB. |
| |
| THE 1ST REVIEW COMMENTS THAT WERE NOT ADDRESSED ARE |
| LISTED BELOW. |
| |
| 2) GAS RISER: |
| |
| C) LIST THE PIPE SIZING TABLES USED FOR EACH TYPE OF |
| PIPE IN THE SYSTEM- 402.2 & 402.3. CSST PIPE TABLE NOT |
| LISTED. |
| |
| E) LABEL THE WATER HEATER AND COOKING APPLIANCES AS |
| EITHER NEW OR EXISTING- SECTION 107.2.1 WPB. |
| |
| F) SHOW THE LOCATIONS OF APPLIANCE SHUT OFF VALVES- |
| SECTION 409.5 FBC FG. |
| |
| 4) LABEL THE HEATER AS EITHER STORAGE TANK OR TANKLESS |
| ON THE RISER, AND PROVIDE VENTING SPECIFICATIONS- |
| SECTIONS 624.1 AND 503.1 FBC FG. |
| |
| 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW |
| THE AIR WILL BE PROVIDED- SECTION 304.1 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| CCOLE@WPB |
| |