2021-02-10 10:52:58 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21020232 |
| 2/10/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE REVIEW THE ENGINEER OF RECORD'S NOTE ON SHEET |
| P.1 OF THE APPROVED RESTAURANT PLANS UNDER PERMIT |
| 20071220. THE ENGINEER SPECIFIED THE CONTRACTOR SHALL |
| SUBMIT A SEPARATE GAS PERMIT AND PLAN INCLUDING "AN |
| ISOMETRIC DRAWING WITH PIPE SIZES, MATERIALS & LENGTHS, |
| THE TYPE OF GAS, THE BTUH LOAD FOR EACH APPLIANCE, THE |
| SIZING TABLES USED, & SPEC SHEETS/INSTALLATION MANUAL |
| FOR THE GAS EQUIPMENT & APPLIANCES." THE SUBMITTED |
| ISOMETRIC IS INCOMPLETE ACCORDING TO THE NOTE AND ALSO |
| SECTION 401.3 & 401.4 FBC FG. |
| |
| 2) GAS RISER: |
| A) SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM |
| THE METER TO THE MOST REMOTE OUTLET, AND THE BRANCH |
| PIPING LENGTHS TO EACH APPLIANCE- SECTION 402.4.1 & |
| 402.4.2 FBC FG. |
| B) SHOW THE TYPES OF PIPING USED IN THE SYSTEM- 403.1. |
| C) SHOW THE DELIVERY PRESSURE AT THE METER AND PIPE |
| SIZING TABLES USED FOR EACH TYPE OF PIPE IN THE SYSTEM- |
| 402.2 & 402.3. |
| D) SHOW THE BTUH LOAD OF THE WATER HEATER AND THE LOAD |
| OF EACH COOKING APPLIANCE- 402.1. |
| E) LABEL THE WATER HEATER AND COOKING APPLIANCES AS |
| EITHER NEW OR EXISTING- SECTION 107.2.1 WPB. |
| F) SHOW THE LOCATIONS OF APPLIANCE SHUT OFF VALVES- |
| 409.5 |
| G) SHOW THE LOCATIONS OF REGULATORS- 410.1 & 410.2 |
| H) SHOW THE LOCATION OF THE AUTO SHUTOFF VALVE FOR THE |
| GAS TO THE COOKING LINE- SEC.10.4.1 NFPA 96. |
| |
| 3) THE UNDERGROUND CSST IS PROHIBITED UNLESS IT IS |
| ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC OR STEEL |
| PIPE, OR OTHER APPROVED MATERIALS- SECTION 404.14. |
| PLEASE INDICATE THE GAS PIPE AND CONDUIT WILL BE BURIED |
| A MINIMUM OF 12 INCHES BELOW GRADE, WILL BE PROTECTED |
| FROM CORROSION- SECTIONS 404.11 & 404.12 FBC FG. |
| |
| 4) AS NOTED IN COMMENT #1 PLEASE SUBMIT SPECS FOR THE |
| WATER HEATER AND THE COOKING APPLIANCES- SECTIONS 301.3 |
| & 305.1 FBC FG. ALL APPLIANCES SHALL BE LISTED AND |
| LABELED. LABEL THE HEATER AS EITHER STORAGE TANK OR |
| TANKLESS ON THE RISER, AND PROVDE VENTING |
| SPECIFICATIONS- SECTIONS 624.1 AND 503.1 FBC FG. |
| |
| 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW |
| THE AIR WILL BE PROVIDED- SECTION 304.1 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| CCOLE@WPB |
| |
2021-02-10 09:27:23 | THE SUBMITTTED GAS DRAWING IS SEVERELY DEFICIENT WITH |
| REQUIRED INFORMATION. PLEASE SUBMIT THE FOLLWING |
| INFORMATION: |
| 1) |