Plan Review Notes
Plan Review Notes For Permit 21020232
Permit Number 21020232
Review Stop G
Sequence Number 1
Notes
Date Text
2021-02-10 10:52:581ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020232
 2/10/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVIEW THE ENGINEER OF RECORD'S NOTE ON SHEET
 P.1 OF THE APPROVED RESTAURANT PLANS UNDER PERMIT
 20071220. THE ENGINEER SPECIFIED THE CONTRACTOR SHALL
 SUBMIT A SEPARATE GAS PERMIT AND PLAN INCLUDING "AN
 ISOMETRIC DRAWING WITH PIPE SIZES, MATERIALS & LENGTHS,
 THE TYPE OF GAS, THE BTUH LOAD FOR EACH APPLIANCE, THE
 SIZING TABLES USED, & SPEC SHEETS/INSTALLATION MANUAL
 FOR THE GAS EQUIPMENT & APPLIANCES." THE SUBMITTED
 ISOMETRIC IS INCOMPLETE ACCORDING TO THE NOTE AND ALSO
 SECTION 401.3 & 401.4 FBC FG.
  
 2) GAS RISER:
 A) SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM
 THE METER TO THE MOST REMOTE OUTLET, AND THE BRANCH
 PIPING LENGTHS TO EACH APPLIANCE- SECTION 402.4.1 &
 402.4.2 FBC FG.
 B) SHOW THE TYPES OF PIPING USED IN THE SYSTEM- 403.1.
 C) SHOW THE DELIVERY PRESSURE AT THE METER AND PIPE
 SIZING TABLES USED FOR EACH TYPE OF PIPE IN THE SYSTEM-
 402.2 & 402.3.
 D) SHOW THE BTUH LOAD OF THE WATER HEATER AND THE LOAD
 OF EACH COOKING APPLIANCE- 402.1.
 E) LABEL THE WATER HEATER AND COOKING APPLIANCES AS
 EITHER NEW OR EXISTING- SECTION 107.2.1 WPB.
 F) SHOW THE LOCATIONS OF APPLIANCE SHUT OFF VALVES-
 409.5
 G) SHOW THE LOCATIONS OF REGULATORS- 410.1 & 410.2
 H) SHOW THE LOCATION OF THE AUTO SHUTOFF VALVE FOR THE
 GAS TO THE COOKING LINE- SEC.10.4.1 NFPA 96.
  
 3) THE UNDERGROUND CSST IS PROHIBITED UNLESS IT IS
 ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC OR STEEL
 PIPE, OR OTHER APPROVED MATERIALS- SECTION 404.14.
 PLEASE INDICATE THE GAS PIPE AND CONDUIT WILL BE BURIED
 A MINIMUM OF 12 INCHES BELOW GRADE, WILL BE PROTECTED
 FROM CORROSION- SECTIONS 404.11 & 404.12 FBC FG.
  
 4) AS NOTED IN COMMENT #1 PLEASE SUBMIT SPECS FOR THE
 WATER HEATER AND THE COOKING APPLIANCES- SECTIONS 301.3
 & 305.1 FBC FG. ALL APPLIANCES SHALL BE LISTED AND
 LABELED. LABEL THE HEATER AS EITHER STORAGE TANK OR
 TANKLESS ON THE RISER, AND PROVDE VENTING
 SPECIFICATIONS- SECTIONS 624.1 AND 503.1 FBC FG.
  
 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
2021-02-10 09:27:23THE SUBMITTTED GAS DRAWING IS SEVERELY DEFICIENT WITH
 REQUIRED INFORMATION. PLEASE SUBMIT THE FOLLWING
 INFORMATION:
 1)