2021-04-06 09:24:42 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 21020231 |
| 4/6/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A1 & P0.1: GREASE INTERCEPTOR: |
| |
| A) THE GREASE WASTE CALCULATIONS SHOW 30 SEATS HOWEVER |
| THE ARCHITECTURAL FLOOR PLAN SHOWS 36 SEATS. |
| |
| B) THE CALCULATIONS ARE USING A FACTOR OF 10 GALLONS |
| PER SEAT WHICH IS FOR SINGLE SERVICE ARTICLE |
| RESTAURANTS. THE PB BRISKET AND BBQ HAS A FULL DINNER, |
| DESSERT, SALAD, SIDES, AND DRINKS MENU WHICH REQUIRES A |
| FACTOR OF 25 GALLONS PER SEAT. PLEASE SEE SECTION |
| 64E-6.010 FAC. |
| |
| C) P0.1: PLEASE CLARIFY WHICH OF THE TWO GB-75 SCHIER |
| GREASE INTERCEPTORS IS THE EXISTING ONE- THE LEGACY OR |
| THE NEW GREAT BASIN? PLEASE NOTE: THE 653 LB. CAPACITY |
| OF THE LEGACY IS UNDERSIZED BASED ON THE CURRENT |
| CALCULATIONS, AND THE NEW GREAT BASIN HAS A RECENT |
| DESIGN DATE OF JULY 2020. I AM NOT ABLE TO FIND A |
| RECENT PERMIT RECORD FOR A NEW GREASE INTERCEPTOR AT |
| 801 VILLAGE BLVD # 307.IT APPEARS THAT THE EXISTING |
| INTERCEPTOR IS THE UNDERSIZED LEGACY. |
| |
| 2) P3.1: PLEASE CORRECT NOTE #2 WHICH INDICATES AN |
| EXISTING GAS SYSTEM. PLEASE REFER TO SHEET A-1 WHICH |
| SHOWS A NEW GAS METER AND PIPING SYSTEM, AND TO THE |
| RISER DRAWING SUBMITTED BY HI-TECH GAS CONTRACTOR- |
| SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |