Plan Review Notes
Plan Review Notes For Permit 21020231
Permit Number 21020231
Review Stop B
Sequence Number 2
Notes
Date Text
2021-04-06 08:58:27RESTAURANT ALT.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOF TOP EQUIPMENT IS SUBJECT TO GRAVITY AND WIND
 LOADS. FOR DRAWING S1- PLEASE PROVIDE STRUCTURAL
 CALCULATIONS FOR SUCH OR SIGNED AND SEALED STRUCTURAL
 MOUNTING DETAILS FROM AN ARCHITECT OR ENGINEER FBC
 1609. FBC EXISTING BUILDING 707.2ADDITION OR
 REPLACEMENT OF ROOFING OR REPLACEMENT OF EQUIPMENT.
 WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT
 OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS,
 STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR
 EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 2) FBC 1510.10 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10.
  
  