2021-02-25 08:59:38RESTAURANT ALT.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS SHOWING THE DESIGN PER THE CODE IN EFFECT
 (2020 FBC AND ASCE 7-16)
 2) ROOF TOP EQUIPMENT IS SUBJECT TO GRAVITY AND WIND
 LOADS ? PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR SUCH
 OR SIGNED AND SEALED STRUCTURAL MOUNTING DETAILS FROM
 AN ARCHITECT OR ENGINEER FBC 1609 ? FBC EXISTING
 BUILDING 707.2ADDITION OR REPLACEMENT OF ROOFING OR
 REPLACEMENT OF EQUIPMENT.
 WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT
 OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS,
 STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR
 EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 3) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC
 1603.1.4
 4) FBC 1510.10 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10.
 5) A BUILDING PERMIT APPLICATION COMPLETED BY A
 CONTRACTOR LICENSED TO PERFORM THE STRUCTURAL WORK IS
 REQUIRED ? IF THE STRUCTURAL WORK IS ON A SEPARATE
 PERMIT PLEASE PROVIDE THE PERMIT NUMBER.
  