2021-02-08 12:20:23THE FOLLOWING COMMENTS WERE SUBMITTED BY LIEUTENANT
 BRIAN DOLAN, BUREAU OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE:
  
 WHERE ADDITION OR MODIFICATION IS MADE TO AN EXISTING
 SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW
 PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS THAN
 200 PSI (13.8 BAR) FOR 2 HOURS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED. SYSTEM WILL BE
 PLACED IN REGULAR SERVICE PRIOR TO LEAVING SITE FOR THE
 EVENING.
  
  