Plan Review Notes For Permit 21020171 |
Permit Number |
21020171 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-02-08 12:20:23 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LIEUTENANT | | BRIAN DOLAN, BUREAU OF FIRE PREVENTION, WEST PALM BEACH | | FIRE RESCUE: | | | | WHERE ADDITION OR MODIFICATION IS MADE TO AN EXISTING | | SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW | | PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS THAN | | 200 PSI (13.8 BAR) FOR 2 HOURS. | | | | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. SYSTEM WILL BE | | PLACED IN REGULAR SERVICE PRIOR TO LEAVING SITE FOR THE | | EVENING. | | | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | |
|