2021-02-18 10:14:31 | 2ND REVIEW FBC-2020 RES. FUEL GAS. |
| PERMIT- 21020074 |
| 2/18/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE RESUBMITTED GAS PLANS SHALL BEAR THE ELECTRONIC |
| SIGNATURE AND SEAL OF THE ENGINEER OF RECORD- FL. |
| STATUTE 471.025 AND SECTION 61G15-23.005 FAC. |
| |
| 2) THE RESUBMITTED SIGNED AND SEALED GAS RISER SHALL |
| SHOW THE TYPE OF PIPE, PIPE SIZE, AND LENGTH OF PIPE |
| FROM THE PE CONNECTION TO THE POOL HEATER- SECTIONS |
| G2413.3 & G2413.4.1 FBC RES. |
| |
| 3) THE RESUBMITTED PLANS AND RISER DRAWING DO NOT MATCH |
| THE APPROVED PLANS FOR THE GAS SYSTEM UNDER PERMIT |
| 20041097. THE APPROVED RISER DRAWING WAS REDLINED PER |
| THE ENGINEER'S INSTRUCTIONS TO SHOW CORRECT PIPE SIZES, |
| PIPE SIZING TABLES, AND GAS LOADS. THERE ARE NUMEROUS |
| DEFICIENT EHD SIZES FOR THE CSST PIPING. AND INCORRECT |
| PIPE SIZING TABLES. PLEASE SUBMIT THE CORRECT SIGNED |
| AND SEALED GAS RISER DRAWING. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |