Plan Review Notes
Plan Review Notes For Permit 21011168
Permit Number 21011168
Review Stop B
Sequence Number 2
Notes
Date Text
2021-02-27 08:25:58PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? PX3169 / 1&2 FAMILY - SFP306
 INSPECTOR ? BN4338
 BUILDING OFFICIAL ? BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 RE: METAL ROOF
 1. DESIGNER SHALL SELECT MODEL, NUMBER OR NAME OF
 ROOFING SYSTEM FROM SUMMARY OF PRODUCTS.
 (CONTRACT SPECIFIES A 1 INCH, 24 GAUGE SNAP LOCK
 SYSTEM. FL27499-R2 DOES NOT PROVIDE THIS SYSTEM AS AN
 OPTION)
 (SUBMIT PRODUCT APPROVAL WITH SYSTEM SPECIFIED IN
 CONTRACT)
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 RE: FLAT ROOF
 2. PROVIDE ENHANCED FASTENER DENSITIES FOR ZONES 2 AND
 3 PER NOTE 5.7.2 OF THE LIMITATIONS. CALCULATIONS SHALL
 BE PREPARED BY A DESIGN PROFESSIONAL.
 (ZONE 3 DP IS -89.4 PER FBC TABLE R301.2(2), 1-STORY
 STRUCTURE, EXPOSURE B)
 (CONTRACT SPECIFIES 45 MIL. FIBERTITE ROOFING PVC WITH
 A MDP OF -90PSF PER FL4930-R16, SYSTEM W-20, PG. 7 OF
 50)
 (PRODUCT APPROVAL SUBMITTED FOR REVIEW IS FL4930-R17
 WITH A MDP OF -45PSF PER SYSTEM W-20, PG. 2 OF 43,
 LIMITATIONS)
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. UPLOAD EACH NOA SEPERATELY. USE PROPER NAMING
 CONVENTIONS. (2ND REQUEST)
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.