2021-02-10 16:18:11 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21011119 |
| 2/10/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER: |
| A) THE RISER SHALL BE DESIGNED IN COMPLIANCE WITH THE |
| FBC- 2020 7TH EDITION FUEL GAS CODE WHICH WENT INTO |
| EFFECT ON DEC. 31, 2020. PLEASE UPDATE THE 2017 CODE |
| REFERENCES AND THE SUBMIT THE UPDATED PIPE SIZING |
| TABLES SECTION 107.2.1 WPB. |
| |
| B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM- |
| SECTION G2413.4.1 FBC RES. |
| |
| C) SHOW THE FLEX CONNECTOR AT THE GENERATOR AND SUBMIT |
| MANUFACTURER?S SPECIFICATION- SECTIONS G2422.1- |
| G2422.1.5. |
| |
| D) CORRECT THE GENERATOR LOAD TO 306,000 BTU?S BASED ON |
| THE SUBMITTED GENERATOR SPECS- SECTION G2408.1. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |