Date |
Text |
2021-03-22 15:30:27 | PROPERTY IN HISTORIC DISTRICT. SETBACKS FOR MECHANICAL |
| EQUIPTMENT BASED ON ACCESSORY STRUCTURE SETBACKS. |
| |
| PASSED PERMIT. |
2021-02-23 16:12:29 | ZONING PLAN REVIEW |
| ________________________________________ |
| |
| DATE OF REVIEW: |
| ________________________________________ |
| |
| REVIEW STATUS: FAILED |
| ________________________________________ |
| |
| PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN |
| REVIEW COMMENTS: |
| |
| 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED |
| SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING |
| AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION |
| 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE |
| THAN 4 FEET INTO A REQUIRED SETBACK. |
| 2. REQUIRED REAR SETBACK FOR THE SF14-C3 DISTRICT IS, |
| PURSUANT TO ZLDR SEC 94-82, 15 FEET, OR 10 PERCENT OF |
| THE LOT DEPTH, WHICHEVER IS LESS. THE MINIMUM REAR |
| SETBACK FOR THE GENERATOR IS 9.43 FT. |
| |
| ________________________________________ |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD |
| LIKE TO RESUBMIT ELECTRONICALLY, EMAIL |
| [email protected] AND REQUEST TO HAVE YOUR |
| PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG |
| IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. |
| PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU |
| ARE FINISHED UPLOADING. |
| ________________________________________ |
| |
| QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: |
| |
| KIZZI ALEXANDRE, ASSOCIATE PLANNER |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION |
| 401 CLEMATIS STREET - P.O. BOX 3147 |
| WEST PALM BEACH, FLORIDA 33402 |
| |
| P: 561.822.1442 |
| TTY: 800.955.8771 |
| E: [email protected] |
| |
| W: WPB.ORG |
| |