Plan Review Notes
Plan Review Notes For Permit 21010857
Permit Number 21010857
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-01-27 11:19:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET A 201 - THERE ARE NO INDICATION OF SMOKE
 ALARMS OUTSIDE THE NEW CORRIDOR SPACE BY THE 2ND
 BATHROOM.
  
 PER NFPA 101, CH 31. EXISTING APARTMENT BUILDINGS
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 PLEASE REVIEW AND ENSURE THERE IS A SA IN THIS
 LOCATION.
  
  
 2) SHEET A 201 - THE ENTRY DOOR TO THE SPARE BEDROOM
 WAS MOVED. THERE ARE NO INDICATIONS OF A SMOKE ALARM
 WITHIN THIS ROOM AND ANY PREVIOUS LOCATION MAY HAV
 EBEEN AFEECTED BY THE DOOR LOCATION CHANGE..
  
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5,
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA
 IN
 ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO BE
 BATTERY POWERED.
  
 PLEASE REVIEW AND ENSURE THERE IS A SA IN THIS
 LOCATION.
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  