2021-01-27 11:19:47 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| 1) SHEET A 201 - THERE ARE NO INDICATION OF SMOKE |
| ALARMS OUTSIDE THE NEW CORRIDOR SPACE BY THE 2ND |
| BATHROOM. |
| |
| PER NFPA 101, CH 31. EXISTING APARTMENT BUILDINGS |
| |
| 31.3.4.5 SMOKE ALARMS. |
| 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| THROUGHOUT WITH AN |
| EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, |
| SMOKE ALARMS |
| SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS |
| MODIFIED BY 31.3.4.5.2, |
| OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY |
| OF THE BEDROOMS |
| AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING |
| BASEMENTS. |
| |
| PLEASE REVIEW AND ENSURE THERE IS A SA IN THIS |
| LOCATION. |
| |
| |
| 2) SHEET A 201 - THE ENTRY DOOR TO THE SPARE BEDROOM |
| WAS MOVED. THERE ARE NO INDICATIONS OF A SMOKE ALARM |
| WITHIN THIS ROOM AND ANY PREVIOUS LOCATION MAY HAV |
| EBEEN AFEECTED BY THE DOOR LOCATION CHANGE.. |
| |
| 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| THROUGHOUT WITH AN |
| EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR |
| A COMPLETE, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH 31.3.5, |
| SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA |
| IN |
| ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. |
| 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE |
| PERMITTED TO BE |
| BATTERY POWERED. |
| |
| PLEASE REVIEW AND ENSURE THERE IS A SA IN THIS |
| LOCATION. |
| |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| |
| |