2021-02-06 22:10:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL DRAWING INCOMPLETE. NOTE: MORE PLAN |
| REVIEW COMMENTS MAY OCCUR AFTER PLAN RESUBMITTAL. NO |
| LIGHTING PLAN SUBMITTED. FBC 107.2.1 |
| |
| 2. NO SMOKE/CARBON ALARMS SHOWN PER FBC-RE 314&315 |
| |
| 3. RECEPTACLE SPACING INCORRECT FOR KITCHEN ISLAND. |
| RANGE IN ISLAND HAS LESS THAN 12'' BEHIND IT AND IS |
| CONSIDERED "SEPARATE SPACES" TO LEFT AND RIGHT. |
| RECEPTACLES REQUIRED WITHIN 2' OF EACH SIDE OF COOKTOP |
| ON ISLAND NEC 210.52 |
| |
| 4. SEVERAL RECEPTACLES SPACING VIOLATIONS THROUGHOUT |
| CONDO, PROVIDE CORRECTIONS NEC 210.52 |
| |
| 5. PROVIDE ITEMIZED LOAD CALCULATION NOT A LOAD CALC |
| STATING "ALL OTHER LOADS EXCLUDING AC". ALSO SERVICE |
| FOR 1801 S FLAGLER IS 120/208 WYE 3-PHASE. 25.8 KVA |
| LOAD WOULD BE 72AMPS NOT 107 AS SHOWN ON PLAN. PROVIDE |
| ACCURATE LOAD CALC NEC 220. |
| |
| 6. NO AFCI PROTECTION SHOWN PER NEC210.12A&B |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |