Plan Review Notes
Plan Review Notes For Permit 21010857
Permit Number 21010857
Review Stop B
Sequence Number 1
Notes
Date Text
2021-02-02 11:45:56WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010857
 ADD: 1801 S. FLAGLER DR. SUITE: 1010
 CONT: PHILIP E. JOHNSON INC.
 TEL: 561-262-1795
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 02/2021
 ACTION: DENIED
  
 1) THE COVER SHEET:
 1A) UNDER THE HEADING OF PROJECT NAME AND ADDRESS YOU
 HAVE THE JOB LOCATED IN DELRAY BEACH, PLEASE UPDATE
 PLAN TO THE CITY OF WEST PALM BEACH, FL. ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED.
  
 1B) UNDER THE HEADING USE AND OCCUPANCY THE OCCUPANCY
 DECLARED IS A R-3 OCCUPANCY FOR SINGLE FAMILY HOMES.
 PLEASE UPDATE THE PLAN TO THE OCCUPANCY TYPE R-2
 SECTION 310.4 OF THE 2020 FBC-B. APARTMENT HOUSES,
 CONDOMINIUMS, ETC.
  
 1C) UNDER THE HEADING USE AND OCCUPANCY & TYPE OF
 CONSTRUCTION THE OCCUPANCY DECLARED THE CONSTRUCTION
 TYPE AS TYPE II-B. PLEASE REVIEW IN THE 2020 FBC-B
 TABLE 504.4 FOR ALLOWABLE STORIES. THIS IS AN 18-STORY
 BUILDING, THE ONLY CONSTRUCTION TYPE THAT ALLOWS AN 18
 STORY BUILDING IS TYPE I-A CONSTRUCTION.
  
 2) SHEET A-002 THE DEMO PLAN IN NEITHER THE MASTER BATH
 NOR THE GUEST BATH ARE SHOWN EXISTING SHOWERS OR TUBS.
 THE MATER BATH LOOKS LIKE THERE ARE 2 CLOSETS WITHIN
 THE MASTER BATH, ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.2.
  
 3) SHEET A-201 THE FLOOR PLAN SHOWS IN THE MASTER BATH
 A NEW SHOWER AND TUB LOCATION. THE SUBMITTED PLANS DO
 HAVE FIRE ASSEMBLY FOR THROUGH PENETRATIONS OF FIRE
 RATED FLOORS BUT THERE IS NO INFORMATION AS TO THE
 CORING OF THE CONCRETE FLOOR FOR THE NEW THROUGH
 PENETRATION. THESE SLABS ARE POST TENSION SLABS, HOW
 ARE YOU GOING TO KEEP FROM CORING THROUGH A POST
 TENSIONED CHORD. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET A-201 DOES PROVIDE A LEGEND FOR THE TILE
 BACKER BOARD FOR THE SHOWERS BUT THERE IS NO
 INFORMATION AS TO THE HEIGHT OF THE TILE IN THE SHOWER
 AND OR BATHTUB AREAS. 2020 FBC-B SHOWERS & TUBS 1210.3.
 SHOWER COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER
 HEADS SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO
 A HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 5) THE FLOOR PLAN INDICATES NEW FLOOR FINISHES WITH
 NOTE # 9. THERE IS NO NOTE # 9 IN THE MASTER BATH OR
 BATH # 2 AS IF THE FLOORS ARE TO BE REPLACED. PLEASE
 PROVIDE A SQUARE FOOT AREA FOR THE FLOORS BEING
 REPLACED. 107.2.1.2. ADDITIONAL INFORMATION, 109.3
 BUILDING PERMIT VALUATION.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  