2021-01-26 18:10:2001/26/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW WILL
 BE REQUIRED AT THE WATER METER BY A LICENSED CONTRACTOR
 WITH A SEPARATE PERMIT. THE RPZ WILL NEED TO BE
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT AND THE CROSS CONNECTION CONTROL MANUAL PAGE
 11 (C). THIS IS DUE TO THE AUTOFILL, WHICH WILL REQUIRE
 A BACKFLOW (PVB) FOR IT. THIS IS AN ISOLATION BACKFLOW,
 AND IT WILL BE REQUIRED TO BE CERTIFIED BY A LICENSED
 BACKFLOW CONTRACTOR. A REPORT MUST BE FILLED OUT AND BE
 WITH THE PERMIT AT FINAL AS THE INSPECTOR MUST TAKE FOR
 CITY RECORDS.
  
 2. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM ITS
 PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 3. SUBMIT THE POOL PUMP CURVE. IDENTIFY THE PUMP CURVE
 WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING INSTALLED
 ON THIS POOL. THIS IS NEEDED TO CONFIRM THE MAXIMUM
 SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 4. SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 HEAT PUMP, CHLORINATOR, CARTRIDGE FILTER, AND THE PUMP
 PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 5. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC.
 R403.10.4.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  