2021-03-01 17:16:16 | RESIDENTIAL (R3) SUBMITTAL THIRD BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| SUBMITTAL # 21010806 |
| |
| |
| NOTE: |
| SURVEY SUBMITTED SHOWS A NEW TIKI HUT ON THE NORTH WEST |
| CORNER. THERE ARE NO PERMITS FOR THIS CONSTRUCTION. |
| NEED TO APPLY FOR A PERMIT FOR THE CONSTRUCTION OF THE |
| TIKI HUT. |
| |
| RESPONSE: |
| JENNA UPLOADED SEMINOLE EXEMPT CHICKEE HUT INFORMATION |
| UNDER THIS SUBMITTAL. THIS IS NOT WHAT IT WAS REQUESTED |
| ON MY NOTE. SEE NOTE ABOVE. NEED TO SUBMIT A PERMIT |
| APPLICATION FOR ZONING REVIEW. IF IT IS A "CHICKEE" |
| WITHOUT ANY ELECTRICAL, PLUMBING OR OTHER NON WOOD |
| FEATURES, THEN IT IS EXEMPT FROM THE FLORIDA BUILDING |
| CODE BUT STILL NEEDS TO COMPLY WITH THE ZONING |
| REQUIREMENTS. SUBMIT SEPARATE PERMIT APPLICATION WITH |
| THE "CHICKEE" INFORMATION FOR ZONING REVIEW. |
| |
| ORIGINAL COMMENT ON MY FIRST REVIEW: |
| 1- NO CLEAR WHY SUBMITTING ROOFING PRODUCT APPROVALS |
| AND CALCULATIONS. SEPARATE ROOFING PERMIT WAS APPLIED |
| FOR AND THE ROOFING PERMIT IS ALREADY CLOSED. TO AVOID |
| CONFLICT/CONFUSION. IT LOOKS LIKE THIS INFORMATION IS |
| IS NOT REQUIRED. |
| |
| RESPONSE: |
| PER CONVERSATION WITH JENNA, IT WAS DETERMINED THAT |
| THIS SUBMITTAL WILL BE FOCUSED ON THE ELEVATION |
| CERTIFICATE ONLY TO AVOID CONFUSION/CONFLICTS. |
| |
| NOW IT IS NOT CLEAR WHY JENNA IS UPLOADING PRODUCT |
| APPROVALS FOR WINDOW AND DOOR IN THIS SUBMITTAL. AS |
| AGREED WITH JENNA ON LAST PHONE CONVERSATION THIS |
| SUBMITTAL IS ONLY FOR THE ELEVATION CERTIFICATE AND THE |
| SURVEY. |
| TO AVOID MORE CONFUSION, PLEASE UPLOAD THE WINDOW AND |
| DOOR PRODUCT APPROVAL UNDER THE REVISION #21020249 THAT |
| WAS GENERATED ON FEBRUARY 4TH OF THIS YEAR. PERMIT |
| LIBRARIAN IS WAITING FOR THE REVISION FEES TO BE PAID |
| AND THE PRODUCT APPROVALS TO BE UPLOADED IN ORDER TO |
| COMPLETE THIS REVISION PROCESS. PLEASE CONTACT THE |
| PERMIT LIBRARIAN AND COMPLETE THE TASK. |
| |
| |
| NOTE: |
| THE FOLLOWING COMMENTS APPLY TO THE ELEVATION |
| CERTIFICATE AND SURVEY SUBMITTED: |
| |
| ORIGINAL COMMENT: |
| 1- A)SURVEY SUBMITTED IS MISSING THE FINISHED ELEVATION |
| OF THE RESIDENCE AND THE FINISHED ELEVATION OF THE A/C |
| EQUIPMENT. PROVIDE SURVEY WITH COMPLETE INFORMATION. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| NOTE: SURVEYOR TO COORDINATE SURVEY INFORMATION AND |
| ELEVATION CERTIFICATE INFORMATION TO AVOID |
| CONFLICTS/DELAYS. |
| |
| |
| ORIGINAL COMMENT: |
| B)REVISED SURVEY TO HAVE SURVEYORS DIGITAL SIGNATURE OR |
| PROVIDE HARD COPY WITH SURVEYORS |
| ORIGINAL/SEAL/SIGNATURE AS REQUIRED BY SEC. 472 F.S. |
| WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| 2- ELEVATION CERTIFICATE SUBMITTED: |
| A) LOWEST ADJACENT GRADE (LAG) SHOWN ON ITEM C2 (F) |
| DOESN'T MATCH WHAT IS SHOWN ON SURVEY SUBMITTED. REVISE |
| AS REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| NOTE: SURVEYOR TO COORDINATE SURVEY INFORMATION AND |
| ELEVATION CERTIFICATE INFORMATION TO AVOID |
| CONFLICTS/DELAYS. |
| |
| B) HIGHEST ADJACENT GRADE (HAG) SHOWN ON ITEM C2 (G) |
| DOESN'T MATCH WHAT IS SHOWN ON SURVEY SUBMITTED. REVISE |
| AS REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| NOTE: SURVEYOR TO COORDINATE SURVEY INFORMATION AND |
| ELEVATION CERTIFICATE INFORMATION TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 3- SURVEYOR TO REVISE ITEM #A4. THIS IS AN ADDITION TO |
| AN EXISTING RESIDENTIAL BUILDING. SEE ELEVATION |
| CERTIFICATE INSTRUCTIONS AND REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |