2021-01-27 10:38:03 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21010798 |
| 1/27/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A01: PLEASE INDICATE THE GAS METER AS EITHER |
| NEW OR EXISTING AND PROVIDE THE GAS DELIVERY PRESSURE. |
| IS THIS A 2 PSI SYSTEM OR LOW-PRESSURE SYSTEM? SECTION |
| G2412.1 FBC RES. |
| |
| 2) A01: PROVIDE THE PIPE SIZING METHOD OR SIZING TABLES |
| USED IN ACCORDANCE WITH SECTION- G2413.3 FBC RES. |
| |
| 3) A01: PROVIDE THE TOTAL DEVELOPED LENGTH OF THE |
| SYSTEM FROM THE METER TO THE RANGE. THE ISO APPEARS TO |
| INDICATE 44 FT.- G2413.4.1. |
| |
| 4) A01: CSST PIPE SIZING IS BY EHD NOT INCHES- PLEASE |
| PROVIDE THE EHD OF THE 3/4 IN. PIPING- G2415.2 |
| |
| 5) A01: PROVIDE AN ENLARGED GAS MANIFOLD DETAIL AND |
| SUBMIT A PRODUCT SPECIFICATION IF THIS IS A |
| MANUFACTURED AND LISTED PIPE CONNECTOR- SECTION |
| G2415.17.2. |
| |
| 6) A01: SHOW THE TYPE OF PIPING FOR THE FUTURE |
| GENERATOR AND SHOW A GAS TIGHT CAP WILL BE INSTALLED- |
| G2414.1 & G2415.15. PLEASE NOTE THAT THE FUTURE |
| GENERATOR SHALL BE INSTALLED A MINIMUM OF 10 FT. FROM |
| MECHANICAL AND NATURAL AIR INTAKE OPENINGS INTO THE |
| BUILDING INCLUDING DOORS AND OPERABLE WINDOWS- SECTION |
| R303.5.1 FBC RES. |
| |
| 7) SUBMIT PRODUCT DATA SHEETS FOR THE WATER HEATER AND |
| THE RANGE WITH MARKINGS TO SHOW THE BTUH CAPACITIES AND |
| GAS INPUT PRESSURES- G2408.1 & G2448.1. PLEASE NOTE |
| THAT REGULATORS MAY BE REQUIRED BASED ON THE PRESSURE |
| OF THE SYSTEM AND INPUT PRESSURES OF THE APPLIANCES. |
| |
| 8) WHERE REGULATORS ARE REQUIRED, THEY SHALL BE SHOWN |
| ON THE RISER WITH INPUT AND OUTPUT PRESSURES NOTED, AND |
| MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED- |
| G2421. |
| |
| 9) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE |
| NEW RANGE AND PROVIDE A CALCULATION IF INDOOR AIR IS TO |
| BE USED- G2407.1, G2407.5. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |