Plan Review Notes For Permit 21010796 |
Permit Number |
21010796 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-01-29 09:09:26 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PRODUCT APPROVAL SUPPLIED FOR THE TILE ROOFING = | | PLEASE CIRCLE THE TILE ATTACHMENT TO BE USED IN THE | | PRODUCT APPROVAL - IF USING ADHESIVE PLEASE PROVIDE THE | | PRODUCT APPROVAL FOR THE ADHESIVE. | | 2) PLEASE PROVIDE A LETTER FROM THE CONTRACTOR ON | | LETTERHEAD STATING THAT THE ROOF TO WALL CONNECTIONS | | WILL BE PERFORMED PER FBC EXISTING BUILDING 706.8 | | WHEN A ROOF COVERING ON AN EXISTING STRUCTURE WITH A | | SAWN LUMBER, WOOD PLANK OR WOOD STRUCTURAL PANEL ROOF | | DECK IS REMOVED AND REPLACED ON A BUILDING THAT IS | | LOCATED IN THE WIND-BORNE DEBRIS REGION AS DEFINED IN | | THE FLORIDA BUILDING CODE, BUILDING AND THAT HAS AN | | INSURED VALUE OF $300,000 OR MORE OR, IF THE BUILDING | | IS UNINSURED OR FOR WHICH DOCUMENTATION OF INSURED | | VALUE IS NOT PRESENTED, HAS A JUST VALUATION FOR THE | | STRUCTURE FOR PURPOSES OF AD VALOREM TAXATION OF | | $300,000 OR MORE: | | | | (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS | | REQUIRED BY SECTION 706.8.1. | | | | (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION | | SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN | | THE COST OF REROOFING. | | |
|