2021-02-10 16:10:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY
 OPENINGS. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 2) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED
 WILL NOT WORK FOR THE GENERATOR SPECIFICATIONS THAT WAS
 SUBMITTED. THIS PAD IS FOR LARGER 22 KW GENERAC
 GENERATORS. CHECK THE SERIAL NUMBERS, THE DIMENSIONS
 AND WEIGHT OF THE GENERATORS LISTED ON THE PAD
 ENGINEERING FOR COMPATIBLE GENERATORS. PLEASE SUBMIT
 MATCHING DOCUMENTS. FBC 107.2.1
  
  