Notes |
Date |
Text |
2021-02-10 16:10:59 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY | | OPENINGS. R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | 2) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED | | WILL NOT WORK FOR THE GENERATOR SPECIFICATIONS THAT WAS | | SUBMITTED. THIS PAD IS FOR LARGER 22 KW GENERAC | | GENERATORS. CHECK THE SERIAL NUMBERS, THE DIMENSIONS | | AND WEIGHT OF THE GENERATORS LISTED ON THE PAD | | ENGINEERING FOR COMPATIBLE GENERATORS. PLEASE SUBMIT | | MATCHING DOCUMENTS. FBC 107.2.1 | | | | |
|