2021-01-27 13:55:00 | 01/27/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS INTERIOR |
| BUILD-OUT WILL BE AND THE OCCUPANCY LOAD PER THE WPB |
| AMENDMENT TO FBC TO 107.3.5.1.1. |
| |
| 2. WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM |
| SHALL COMPLY WITH 603. WHERE BATHING ROOMS ARE |
| PROVIDED, EACH BATHING ROOM SHALL COMPLY WITH 603. THE |
| BATHROOM ON THE SECOND FLOOR HAS TO COMPLY WITH THE |
| 2020 ACCESSIBILITY CODE; |
| |
| A. THE TURNING SPACE COMPLYING WITH 304 SHALL BE |
| PROVIDED WITHIN THE ROOM PER THE 2020 FBC ACC SECTION |
| 603.2.1. |
| |
| B. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE PER |
| THE 2020 FBC ACC SECTION 60.3.2.3. |
| |
| C. A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED |
| FOR A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED PER THE 2020 ACC |
| FBC SECTION 606.2. |
| |
| D. SHOWER COMPARTMENTS SHALL HAVE SIZES AND CLEARANCES |
| COMPLYING WITH 2020 FBC SECTION 608.2. |
| |
| E. THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNITS SHALL |
| COMPLY WITH 309.4. PER THE 2020 FBC ACC SECTION 608.5. |
| |
| F. THE GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH |
| 609. GRAB BARS SHALL BE PROVIDED ON THE SIDEWALL |
| CLOSEST TO THE WATER CLOSET AND ON THE REAR WALL. |
| PLEASE REFER TO EXCEPTION 1 ON REINFORCEMENT PER THE |
| 2020 FBC SECTION 604.5 (1). |
| |
| 3. THIS IS A 2021 PERMIT, AND ON-PAGE P0.1 AND P3.1, IT |
| REFERS TO THE 2017 CODE. PLEASE CHANGE TO REFER TO THE |
| CURRENT CODE PER THE WPB AMENDMENTS TO FBC 102.4. |
| |
| 4. PLEASE PROVIDE CLEAR FLOOR SPACE FOR ACCESSIBLE |
| EMPLOYEE BRAKE KITCHEN AND GIVE A CABINET HEIGHT DETAIL |
| THAT COMPLIES WITH 2020 FBC ACC SEC. 606.3. |
| |
| 5. ON SHEET P2.1 ON NOTE 3 FOR THE ICEMAKER AND COFFEE |
| MAKER, ADD TO THE NOTE THAT THE BACKFLOW DEVICE SHALL |
| COMPLY WITH THE ASSE 1024 NON-CARBONATED. |
| |
| 6. PLEASE SHOW A HAMMER ARRESTOR FOR THE REFRIGERATOR |
| ICEMAKER TO CONFORM TO ASSE 1010 PER THE 2020 FBC |
| SECTION 609.4. |
| |
| 7. PLEASE SHOW ALL SHUTOFF VALVES ON ISOMETRIC DRAWING |
| PER THE WPB AMENDMENTS TO FBC 107.2.1. |
| |
| 8. PLEASE PROVIDE A SHUTOFF VALVE TO THE RISER TO THE |
| SECOND-FLOOR BATHROOM WITH ACCESS PER THE 2020 FBC |
| SECTION P 606.1(4). |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |