Plan Review Notes
Plan Review Notes For Permit 21010690
Permit Number 21010690
Review Stop M
Sequence Number 1
Notes
Date Text
2021-03-02 10:20:53PLAN REVIEW / MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN SHEET 01 SHOWS MINI SPLIT C/U LOCATED AT REAR
 OF STRUCTURE. PLAN SHEET E-1 SHOWS TWO C/U'S. PLEASE
 CLARIFY?
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. SERVICE OUTLET REQUIRED AT MECH. EQUIPMENT.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 3. PROVIDE A CONDENSATE DISPOSAL PLAN- FBC R M1411.3
 M1411.3 CONDENSATE DISPOSAL.
 CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A
 NUISANCE.
  
  
 4. TIE DOWN
 M1401.4EXTERIOR INSTALLATIONS.
 EQUIPMENT AND APPLIANCES INSTALLED OUTDOORS SHALL BE
 LISTED AND LABELED FOR OUTDOOR INSTALLATION. SUPPORTS
 AND FOUNDATIONS SHALL PREVENT EXCESSIVE VIBRATION,
 SETTLEMENT OR MOVEMENT OF THE EQUIPMENT. SUPPORTS AND
 FOUNDATIONS SHALL BE IN ACCORDANCE WITH SECTION
 M1305.1.4.1.
  
 5. M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 A NOTE ON PLAN WILL SUFFICE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  