2021-02-09 10:38:41 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2, PLEASE CLARIFY THE DETAILS FOR THE LOWER | | CONNECTIONS OF OPENINGS # 4, 6 & 22. | | | | THE PRODUCT APPROVAL INDICATES A TYPE "L" CONNECTION | | WITH 5"O.C. ANCHOR SPACING | | AND THE OPENING SCHEDULE INDICATES A TYPE "H" | | CONNECTION WITH 10" O.C. ANCHOR SPACING |
|