Plan Review Notes For Permit 21010635 |
Permit Number |
21010635 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-25 15:34:44 | WINDOWS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW ON THE FLOOR PLAN IF THE ROOMS ARE OPEN | | WITH NO SEPARATE BEDROOMS. AN EMERGENCY EGRESS IS NOT | | REQUIRED IF THE ROOM DOES NOT CONTAIN A SEPARATE | | BEDROOM. | | 2) DRAWINGS SHOW FIXED WINDOWS TO BE INSTALLED - PLEASE | | SHOW THE EMERGENCY EGRESS TO COMPLY WITH - FBC 1030.1 | | GENERAL. | | IN ADDITION TO THE MEANS OF EGRESS REQUIRED BY THIS | | CHAPTER, PROVISIONS SHALL BE MADE FOR EMERGENCY ESCAPE | | AND RESCUE OPENINGS IN GROUP R-2 OCCUPANCIES IN | | ACCORDANCE WITH TABLES 1006.3.3(1) AND 1006.3.3(2) AND | | GROUP R-3 OCCUPANCIES. BASEMENTS AND SLEEPING ROOMS | | BELOW THE FOURTH STORY ABOVE GRADE PLANE SHALL HAVE AT | | LEAST ONE EXTERIOR EMERGENCY ESCAPE AND RESCUE OPENING | | IN ACCORDANCE WITH THIS SECTION. | | |
|