2021-03-08 08:02:10 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21010552 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SHOW THAT THE KITCHEN EXHAUST TERMINATION IS |
| A MINIMUM OF 3? FROM ANY OPERABLE OPENS INTO THE |
| RESIDENCE. FBC RES M1502.3 |
| |
| 2) PERMIT APPLICATION IS FOR KITCHEN EXHAUST INCLUDING |
| MAKE-UP AIR PLEASE PROVIDE MORE INFORMATION. WHAT IS |
| THE CFM REQUIRED FOR THE RANGE? IS THERE A DAMPER ON |
| THE MAKE UP AIR INTAKE? IF SO HOW IS IT OPENED? FBC RES |
| M1503 |
| |
| 3) ONE LIKE FOR LIKE CHANGE OUT WAS SUBMITTED FOR THE |
| 3-TON UNIT, IS THE 2.5 TON UNIT TO BE CHANGED OUT ALSO? |
| IF THIS PERMIT IS TO INCLUDE MECHANICAL SYSTEM CHANGE |
| OUTS PLEASE MAKE THIS SUBMITTAL CLEAR AS TO EXACTLY |
| WHAT IS BEING DONE ON THIS PROJECT. THERE IS |
| INFORMATION SUBMITTED FOR UNIT 1 BUT NOTHING FOR UNIT |
| 2. PLEASE LABEL EACH UNIT ON THE DRAWINGS. |
| |
| 4) THIS WORK WILL ALSO REQUIRE AN ELECTRICAL PERMIT AND |
| REVIEW. |
| |
| 5) THE DESIGNER OF THE DRAWINGS MUST INCLUDE THEIR NAME |
| AND SIGNATURE ON EACH SHEET. |
| PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN |
| (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE |
| SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE |
| DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE |
| WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE |
| CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET |
| MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL |
| TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |