Plan Review Notes
Plan Review Notes For Permit 21010419
Permit Number 21010419
Review Stop B
Sequence Number 1
Notes
Date Text
2021-02-01 13:15:16GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE GENERATOR EXHAUST DISTANCE FROM A
 BUILDING OPENING TO COMPLY WITH FBC R303.5.1 INTAKE
 OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 2) GENERATOR SLAB DRAWINGS DO NOT SHOW THE GENERATOR
 MODEL NUMBER (7210).
  