2021-02-22 11:09:03 | 1ST REVIEW FBC-2020 RES. |
| PERMIT-21010413 |
| 2/22/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET C1.0: PLEASE UPDATE THE CODE REFERENCES- THE |
| FBC- 2020 7TH EDITION CODES WENT INTO EFFECT ON |
| 12/31/20. |
| |
| 2) SHEET S1.0 SANITARY RISER: SHOW THE REQUIRED |
| CLEANOUT AT THE JUNCTION OF THE CABANA DRAIN AND SEWER- |
| SECTION P3005.2.3 FBC RES. |
| |
| 3) S1.0: PROVIDE A WATER PLAN AND RISER DRAWING SHOWING |
| THE POINT OF CONNECTION TO THE CITY SERVICE- SECTIONS |
| 107.2.1 AND 107.3.5.3 FBC RES. PLEASE NOTE THAT A |
| BACKFLOW PREVENTER MAY BE REQUIRED AT THE SERVICE |
| ACCORDING TO CITY OF WEST PALM CROSS UTILITIES |
| DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM. |
| MULTI-FAMILY DWELLING, AND WATER USERS WILL BE REQUIRED |
| TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT |
| OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY REQUIRED |
| WILL BE DEPENDENT UPON THE DEGREE OF HAZARD POSED BY |
| THE WATER USER. FOR FURTHER INFORMATION CONTACT THE WPB |
| UTILITIES DEPT. AT 561-822-2210. |
| |
| PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| |
| 4) S1.0: SHOW THE SOURCE OF HOT WATER FOR THE PLUMBING |
| FIXTURES- SECTION P2801.1 FBC RES. CLARIFY IF A NEW |
| WATER HEATER WILL BE INSTALLED- SHOW THE LOCATION OF |
| THE UNIT, PROVIDE AN EQUIPMENT SCHEDULE, AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- TABLE C404.2 FBC EC. |
| PLEASE NOTE THAT A SEPARATE PRIMARY OR SUB GAS PERMIT |
| WILL BE REQUIRED FOR GAS WATER HEATERS- SECTION 105.1 |
| WPB. AT THE PRESENT TIME NO GAS PLANS HAVE BEEN |
| SUBMITTED. |
| |
| 5) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & |
| P2709.2 FBC RES. |
| |
| 6) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. |
| |
| 7) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| 105.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |