Plan Review Notes
Plan Review Notes For Permit 21010413
Permit Number 21010413
Review Stop E
Sequence Number 1
Notes
Date Text
2021-02-19 13:55:44PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. R404.1LIGHTING EQUIPMENT (MANDATORY).
 NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY
 HIGH-EFFICACY LAMPS.
 EXCEPTION: LOW-VOLTAGE LIGHTING.
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 2. OUTLET WALL SPACING. PLAN SHOWS OUTLET WHERE THERE
 IS NO WALL. CHECK SPACING OF WALL OUTLETS.
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
 3. PROVIDE OUTLETS AT FRONT AND REAR OF UNIT.
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
  
 4. IDENTIFY LOCATION OF NEW PANEL A AT EXISTING 1-STORY
 RESIDENCE..
  
 5. PROVIDE LOCATION OF EXISTING 100A DISCONENCT AT
 PROPOSED CABANA.
 FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
  
 6. PROVIDE EQUIPMENT SERVICE OUTLET FOR CU-1
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 7. IDENTIFY LOCATION OF WATER HEATER AND DISCONNECT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. INCLUDE THE FOLLOWING STATEMENT ON ELECTRICAL PLAN.
 AFCI OUTLETS
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16
  
 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. .
 NEC 406.12; FBC RE E4002.14 A NOTE ON PLAN WILL SUFFICE
  
 11. SMOKE ALARMS
 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING.
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 12. PROVIDE 2 SMALL APPLIANCE CIRCUTS.
 E3901.3 SMALL APPLIANCE RECEPTACLES.
 IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR
 SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE
 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND
 E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR
 REFRIGERATION APPLIANCES. [210.52(B)(1)]
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  