2021-02-19 13:55:44 | PLAN REVIEW / ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. R404.1LIGHTING EQUIPMENT (MANDATORY). |
| NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY |
| HIGH-EFFICACY LAMPS. |
| EXCEPTION: LOW-VOLTAGE LIGHTING. |
| A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| |
| 2. OUTLET WALL SPACING. PLAN SHOWS OUTLET WHERE THERE |
| IS NO WALL. CHECK SPACING OF WALL OUTLETS. |
| E3901.2.1 SPACING. |
| RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| OUTLET. [210.52(A)(1)] |
| |
| 3. PROVIDE OUTLETS AT FRONT AND REAR OF UNIT. |
| E3901.7 OUTDOOR OUTLETS. |
| NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| |
| 4. IDENTIFY LOCATION OF NEW PANEL A AT EXISTING 1-STORY |
| RESIDENCE.. |
| |
| 5. PROVIDE LOCATION OF EXISTING 100A DISCONENCT AT |
| PROPOSED CABANA. |
| FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, |
| 225.32 |
| |
| 6. PROVIDE EQUIPMENT SERVICE OUTLET FOR CU-1 |
| E3901.12 HVAC OUTLET. |
| A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| MEANS. (210.63) |
| |
| 7. IDENTIFY LOCATION OF WATER HEATER AND DISCONNECT. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 8. INCLUDE THE FOLLOWING STATEMENT ON ELECTRICAL PLAN. |
| AFCI OUTLETS |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC |
| 210.12; FBC RE E3902.16 |
| |
| 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| |
| 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. . |
| NEC 406.12; FBC RE E4002.14 A NOTE ON PLAN WILL SUFFICE |
| |
| 11. SMOKE ALARMS |
| 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING. |
| R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| 12. PROVIDE 2 SMALL APPLIANCE CIRCUTS. |
| E3901.3 SMALL APPLIANCE RECEPTACLES. |
| IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR |
| SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE |
| 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY |
| SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR |
| RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND |
| E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR |
| REFRIGERATION APPLIANCES. [210.52(B)(1)] |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |