2021-01-20 10:19:41 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THIS PERMIT WAS APPLIED FOR AFTER DECEMBER 31, 2020. | | IT IS REQUIRED TO COMPLY WITH THE CURRENT CODE WHICH IS | | THE 2020 FBC. SUBMIT PRODUCT APPROVALS THAT REFERENCE | | THE 2020 FBC. FBC 107.3.4 | | | | 2) ON THE PRODUCT APPROVAL FOR THE FLAT ROOF, PLEASE | | HI-LIGHT OR CIRCLE THE SYSTEM AND THE MAXIMUM DESIGN | | PRESSURE FOR IT. IF ENHANCED FASTENING IS REQUIRED FOR | | THE PERIMETER AND CORNERS, SUBMIT SIGNED AND SEALED RAS | | 117 CALCULATIONS. FBC 107.2.1 | | | | | | | | | | | | | | | | | | |
|