2021-01-28 11:36:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SUBMIT A PLAN SHOWING LOCATION OF AC DISCONNECT AND
 SIZE. CHRIS CAN DRAW THIS DOES NOT NEED TO ARCHITECT OR
 ENGINEER.
  
 2) MISC WORK DOES NOT TELL US WHAT IS BEING DONE, IF IT
 IS JUST SOME GENERAL REPAIRS OR REPLACEMENTS SHOW
 LOCATION ON SAME PLAN AS AC DISCONNECT. THIS IS JUST SO
 THE INSPECTOR WILL KNOW WHAT TO LOOK FOR IN CASE YOU
 ARE NOT ON SITE AT THE TIME OF INSPECTION.
  
 3) MAKE SURE CHRIS PRINTS HIS NAME ON PLAN , SIGN HIS
 NAME ON PLAN AND DATE IT.