Plan Review Notes
Plan Review Notes For Permit 21010326
Permit Number 21010326
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-01 09:05:44SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS TO SHOW THE DESIGN CRITERIA BASED ON THE
 CODE IN EFFECT (2020 FBC AND ASCE 7-16)
 2) PLEASE SHOW THE SMOKE ALARM LOCATIONS THROUGH OUT
 THE EXISTING HOUSE TO COMPLY WITH FBC R314.2.2
 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 3) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG
 WINDOWS (02-1120.03) HAS EXPIRED - PLEASE PROVIDE AN
 UPDATED VERSION.
 4) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE
 ROOFING SYSTEM.
 5) ALL PRODUCT APPROVALS AND SHOP DRAWINGS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD.
 6) THE DESIGN CRITERIA FOR THE TRUSS DRAWINGS SHOWN ON
 THE TRUSS ENGINEERING NEEDS TO BE REVISED TO REFLECT
 THE CODE IN EFFECT (2021 FBC AND ASCE 7-16)
  
  
  