2021-03-01 08:37:212ND REVIEW FBC-2020 RES.
 PERMIT- 21010298
 3/1/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RISER SHOWS UNDERSIZED PIPING FROM THE RISER TO
 THE GENERATOR. REFER TO TABLE 402.4(2) FBC FG- A
 MINIMUM 1-1/2 IN. GALVANIZED PIPE IS REQUIRED. PLEASE
 NOTE THE EXISTING SYSTEM HAS A TOTAL LOAD OF 1292 MBTUH
 AT A DEVELOPED LENGTH OF 70 FT. PLEASE SEE THE RECORD
 APPROVED PLANS UNDER PERMIT #06050871.
  
 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  