Plan Review Notes For Permit 21010298 |
Permit Number |
21010298 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-03-01 08:37:21 | 2ND REVIEW FBC-2020 RES. | | PERMIT- 21010298 | | 3/1/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE RISER SHOWS UNDERSIZED PIPING FROM THE RISER TO | | THE GENERATOR. REFER TO TABLE 402.4(2) FBC FG- A | | MINIMUM 1-1/2 IN. GALVANIZED PIPE IS REQUIRED. PLEASE | | NOTE THE EXISTING SYSTEM HAS A TOTAL LOAD OF 1292 MBTUH | | AT A DEVELOPED LENGTH OF 70 FT. PLEASE SEE THE RECORD | | APPROVED PLANS UNDER PERMIT #06050871. | | | | 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING | | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 | | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|